A SEMINAR PRESENTATION
ON
“CONCEPT OF SYMMETRICAL
COMPONENT AS A TECHNIQUE FOR
ANALYSIS OF FAULT AND
IMPROVEMENT OF OVERCURRENT
PROTECTION SCHEME”
Submitted to: Submitted by:
Mr. Ankush Tandon Saurabh Varshney
Mrs. Deepti Arela (10ESKEE106) 1
CONTENT
 INTRODUCTION
 PROTECTION SYSTEM
 SYMMETRICAL COMPONENT
 FAULT
 OVERCURRENT RELAY
 ALGORITHM
 SIMULATION DISTRIBUTION SYSTEM
 RESULTS
 CONCLUSION 2
INTRODUCTION
 Aim of my seminar topic is better
understanding the concept of symmetrical
components for enhancing protection
scheme by providing a practical technology
for understanding and analyzing power
system operation during unbalanced
condition.
3
PROTECTION SYSTEM
What is need of protective system ?
 In order to maintain steady state of
power system by taking correct and
quick remedial action during any faulty
condition.
Properties of a good protective system
Automatic
Quick
Minimum amount of disruption 4
SYMMETRICAL COMPONENT
 Unbalanced systems are difficult to handle.
 It provide balanced analysis of an unbalanced
system
 The unbalanced three phase system can be
transformed into three balanced phasors
 Positive Sequence
 Negative Sequence
 Zero Sequence
5
POSITIVE PHASE SEQUENCE
 Each have the same magnitude.
 Each positive sequence voltage or
current quantity is displaced 120
from one another.
 The positive sequence quantities
have a-b-c, counter clock-wise,
phase rotation.
6
NEGATIVE PHASE SEQUENCE
 Each have the same magnitude.
 Each negative sequence voltage
or current quantity is displaced 120
from one another.
 The negative sequence quantities
have a-c-b, counter clock-wise,
phase rotation.
7
ZERO PHASE SEQUENCE
 Each zero sequence quantity has the same magnitude.
 All three phasor with no angular
displacement between them, all in phase.
8
9
FAULT
o General Causes of fault
 Fault due to lightning
 Tree limbs falling on the line
 Wind damage
 Effects of fault
 Flow of excessive current
 Abnormal voltages
 Induces over voltages on neighbouring
equipments.
 Hazards to human, equipment and animals
TYPES OF FAULTS
• Balanced Faults :
– Three-phase fault
• Unbalanced Faults :
– Single line to ground fault
– Line to line fault
– Double line to ground fault
10
UNBALANCED FAULTS
11
SINGLE LINE TO GROUND FAULT
 The most common type of fault is the single line to
ground fault:
12
13
 The SLG fault can be described by the following
voltage and current relationship:
Ib=0 & Ic=0
Va=IaZf
 The Sequence current can be given as:
LINE TO LINE FAULT
 It occurs when two conductors are short circuited.
 There is no zero sequence component due to
absence of ground return path.
 The positive and negative sequence components
are connected in parallel.
14
DOUBLE LINE TO GROUND FAULT
 In double line to ground fault two line conductors
come in contact with each other and ground .
 The networks are connected in parallel.
 For the zero sequence component it requires to add
an external impedance of Zf+3Zg
15
OVER CURRENT RELAY
 Short-circuit currents are generally several times (5
to 20) full load current. Hence fast fault clearance is
always desirable on short circuits.
 A relay that operates or picks up when it’s current
exceeds a predetermined value (setting value) is
called Over current Relay.
 Over current includes short-circuit protection, and
short circuits can be:
 Phase faults
 Earth faults
 Winding faults
16
TYPES OF OVER CURRENT RELAY
I. Instantaneous Over current (Definite Current)
Relay
II. Definite Time Over current Relay
III. Inverse Time Over current Relay (IDMT
Relay)
i. Moderately Inverse
ii. Very Inverse Time
iii. Extremely Inverse
IV. Directional over current Relay
17
ALGORITHM
 The criterion function for discriminating fault from
non fault switching is defined as follows :
R= |I1|-|I2| / |I1|+|I2|
18
SIMULATED DISTRIBUTION SYSTEM
19
RESULTS
Several non faults events are applied to
this system along with some short circuit
events a different time.
The discrimination of fault from a non
fault event could be done by representing
two cases
 Transformer energizing
 Fault
20
TRANSFORMER ENERGIZING
 Various inrush current condition were simulated.
 Various parameters which have considerable effect
on the characteristic of the current signal were
changed and was analysed.
FAULT
 In this case a single line to ground fault occurs.
21
22
NON FAULT CONDITION
WHEN VALUE OF R>=.35s
FAULTY CONDITION WHEN
VALUE OF R<.35s
23
THREE PHASE CURRENT
BEFORE FAULT
THREE PHASE CURRENT
AFTER FAULT
CONCLUSION
 Simple method of improving over current relays
operation by algorithm, based on different
behaviour of the current amplitudes. Based on
the differences, a criterion function R is defined
such that undesirable operation of the over
current relays to the switching is prevented.
24
THANK YOU
ANY QUERIES?
25

Mais conteúdo relacionado

Mais procurados

Mais procurados (20)

File 1 power system fault analysis
File 1 power system fault analysisFile 1 power system fault analysis
File 1 power system fault analysis
 
Symmertical components
Symmertical componentsSymmertical components
Symmertical components
 
Fault Calculations
Fault CalculationsFault Calculations
Fault Calculations
 
ppt of Three phase fault analysis with auto reset for temporary fault and tri...
ppt of Three phase fault analysis with auto reset for temporary fault and tri...ppt of Three phase fault analysis with auto reset for temporary fault and tri...
ppt of Three phase fault analysis with auto reset for temporary fault and tri...
 
Unsymmetrical fault in transmission line
Unsymmetrical fault in transmission lineUnsymmetrical fault in transmission line
Unsymmetrical fault in transmission line
 
A step-by-step approach to prepare fault studies of electrical power systems
A step-by-step approach to prepare fault studies of electrical power systemsA step-by-step approach to prepare fault studies of electrical power systems
A step-by-step approach to prepare fault studies of electrical power systems
 
Calculation of short circuit currents
Calculation of short circuit currents Calculation of short circuit currents
Calculation of short circuit currents
 
Balanced faults
Balanced faultsBalanced faults
Balanced faults
 
Calculation of short_circuit_currents
Calculation of short_circuit_currentsCalculation of short_circuit_currents
Calculation of short_circuit_currents
 
Short circuit calculations
Short circuit calculationsShort circuit calculations
Short circuit calculations
 
Short circuit (wic) testing and parameters.
Short circuit (wic) testing and parameters.Short circuit (wic) testing and parameters.
Short circuit (wic) testing and parameters.
 
Symmetrical components......
Symmetrical components......Symmetrical components......
Symmetrical components......
 
Analysis of unsymmetrical faults using the bus impedance matrix, Faults throu...
Analysis of unsymmetrical faults using the bus impedance matrix, Faults throu...Analysis of unsymmetrical faults using the bus impedance matrix, Faults throu...
Analysis of unsymmetrical faults using the bus impedance matrix, Faults throu...
 
Analysis of unsymmetrical faults using bus impedence matrix
Analysis of unsymmetrical faults using bus impedence matrixAnalysis of unsymmetrical faults using bus impedence matrix
Analysis of unsymmetrical faults using bus impedence matrix
 
symmetrical component of power system
symmetrical component of power systemsymmetrical component of power system
symmetrical component of power system
 
Basic short circuit calculation procedure
Basic short circuit calculation procedureBasic short circuit calculation procedure
Basic short circuit calculation procedure
 
Three Phase Fault Analysis With Auto Reset On Temporary Fault And Permanent Trip
Three Phase Fault Analysis With Auto Reset On Temporary Fault And Permanent TripThree Phase Fault Analysis With Auto Reset On Temporary Fault And Permanent Trip
Three Phase Fault Analysis With Auto Reset On Temporary Fault And Permanent Trip
 
Power systems symmetrical components
Power systems symmetrical componentsPower systems symmetrical components
Power systems symmetrical components
 
Short circuit followup[1]
Short circuit followup[1]Short circuit followup[1]
Short circuit followup[1]
 
Symmetrical component method for 3 phase power representation
Symmetrical component method for 3 phase power representationSymmetrical component method for 3 phase power representation
Symmetrical component method for 3 phase power representation
 

Destaque

Fault Level Calculation
Fault Level CalculationFault Level Calculation
Fault Level Calculation
Dinesh Sarda
 
FAULT DETECTION AND CLASSIFICATION ON TRANSMISSION OVERHEAD LINE USING BPP...
FAULT DETECTION AND CLASSIFICATION ON TRANSMISSION OVERHEAD LINE  USING BPP...FAULT DETECTION AND CLASSIFICATION ON TRANSMISSION OVERHEAD LINE  USING BPP...
FAULT DETECTION AND CLASSIFICATION ON TRANSMISSION OVERHEAD LINE USING BPP...
Politeknik Negeri Ujung Pandang
 
protection of transmission lines[distance relay protection scheme]
protection of transmission lines[distance relay protection scheme]protection of transmission lines[distance relay protection scheme]
protection of transmission lines[distance relay protection scheme]
moiz89
 
RELAY CO-ORDINATION WITH FAULT CALCULATION
RELAY CO-ORDINATION WITH FAULT CALCULATIONRELAY CO-ORDINATION WITH FAULT CALCULATION
RELAY CO-ORDINATION WITH FAULT CALCULATION
Md Sarowar Alam
 

Destaque (14)

Fault Level Calculation
Fault Level CalculationFault Level Calculation
Fault Level Calculation
 
Unsymmetrical fault analysis 2003 final new 2007
Unsymmetrical fault analysis 2003 final new 2007Unsymmetrical fault analysis 2003 final new 2007
Unsymmetrical fault analysis 2003 final new 2007
 
Power system fault analysis ppt
Power system fault analysis pptPower system fault analysis ppt
Power system fault analysis ppt
 
Unsymmetrical Fault
Unsymmetrical FaultUnsymmetrical Fault
Unsymmetrical Fault
 
Power System Analysis!
Power System Analysis!Power System Analysis!
Power System Analysis!
 
Basics of overcurrent protection
Basics of overcurrent protectionBasics of overcurrent protection
Basics of overcurrent protection
 
FAULT DETECTION AND CLASSIFICATION ON TRANSMISSION OVERHEAD LINE USING BPP...
FAULT DETECTION AND CLASSIFICATION ON TRANSMISSION OVERHEAD LINE  USING BPP...FAULT DETECTION AND CLASSIFICATION ON TRANSMISSION OVERHEAD LINE  USING BPP...
FAULT DETECTION AND CLASSIFICATION ON TRANSMISSION OVERHEAD LINE USING BPP...
 
load flow 1
 load flow 1 load flow 1
load flow 1
 
protection of transmission lines[distance relay protection scheme]
protection of transmission lines[distance relay protection scheme]protection of transmission lines[distance relay protection scheme]
protection of transmission lines[distance relay protection scheme]
 
power system analysis PPT
power system analysis PPTpower system analysis PPT
power system analysis PPT
 
Power system analysis (III-EEE)
Power system analysis  (III-EEE)Power system analysis  (III-EEE)
Power system analysis (III-EEE)
 
Economic operation of Power systems by Unit commitment
Economic operation of Power systems by Unit commitment Economic operation of Power systems by Unit commitment
Economic operation of Power systems by Unit commitment
 
three phase fault analysis with auto reset for temporary fault and trip for p...
three phase fault analysis with auto reset for temporary fault and trip for p...three phase fault analysis with auto reset for temporary fault and trip for p...
three phase fault analysis with auto reset for temporary fault and trip for p...
 
RELAY CO-ORDINATION WITH FAULT CALCULATION
RELAY CO-ORDINATION WITH FAULT CALCULATIONRELAY CO-ORDINATION WITH FAULT CALCULATION
RELAY CO-ORDINATION WITH FAULT CALCULATION
 

Semelhante a CONCEPT OF SYMMETRICAL COMPONENT AS A TECHNIQUE FOR ANALYSIS OF FAULT AND IMPROVEMENT OF OVERCURRENT PROTECTION SCHEME

Relay operation principles
Relay operation principlesRelay operation principles
Relay operation principles
Ammar Al Hakeim
 
Matlab Simulink in Three-Phase Fault Analysis on Transmission line
Matlab Simulink in Three-Phase Fault Analysis on Transmission lineMatlab Simulink in Three-Phase Fault Analysis on Transmission line
Matlab Simulink in Three-Phase Fault Analysis on Transmission line
pamu17
 

Semelhante a CONCEPT OF SYMMETRICAL COMPONENT AS A TECHNIQUE FOR ANALYSIS OF FAULT AND IMPROVEMENT OF OVERCURRENT PROTECTION SCHEME (20)

SHORT CIRCUIT ANALYSIS OF ELECTRICAL DISTRIBUTION SYSTEM FOR INDUSTRY APPLICA...
SHORT CIRCUIT ANALYSIS OF ELECTRICAL DISTRIBUTION SYSTEM FOR INDUSTRY APPLICA...SHORT CIRCUIT ANALYSIS OF ELECTRICAL DISTRIBUTION SYSTEM FOR INDUSTRY APPLICA...
SHORT CIRCUIT ANALYSIS OF ELECTRICAL DISTRIBUTION SYSTEM FOR INDUSTRY APPLICA...
 
Power System Protection course - Part I
Power System Protection course - Part IPower System Protection course - Part I
Power System Protection course - Part I
 
Relay operation principles
Relay operation principlesRelay operation principles
Relay operation principles
 
TOPIC 6.2- Power System Faults and Protection System.pptx
TOPIC 6.2- Power System Faults and Protection System.pptxTOPIC 6.2- Power System Faults and Protection System.pptx
TOPIC 6.2- Power System Faults and Protection System.pptx
 
Consideration of Three Phase Faults on Transmission Line with Distance Protec...
Consideration of Three Phase Faults on Transmission Line with Distance Protec...Consideration of Three Phase Faults on Transmission Line with Distance Protec...
Consideration of Three Phase Faults on Transmission Line with Distance Protec...
 
CHAPTER- 4.ppt
CHAPTER- 4.pptCHAPTER- 4.ppt
CHAPTER- 4.ppt
 
ECE4762011_Lect22.ppt
ECE4762011_Lect22.pptECE4762011_Lect22.ppt
ECE4762011_Lect22.ppt
 
Azizan_2020_IOP_Conf._Ser.__Mater._Sci._Eng._767_012004.pdf
Azizan_2020_IOP_Conf._Ser.__Mater._Sci._Eng._767_012004.pdfAzizan_2020_IOP_Conf._Ser.__Mater._Sci._Eng._767_012004.pdf
Azizan_2020_IOP_Conf._Ser.__Mater._Sci._Eng._767_012004.pdf
 
ECE610 IEEE
ECE610 IEEEECE610 IEEE
ECE610 IEEE
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and Development
 
Matlab Simulink in Three-Phase Fault Analysis on Transmission line
Matlab Simulink in Three-Phase Fault Analysis on Transmission lineMatlab Simulink in Three-Phase Fault Analysis on Transmission line
Matlab Simulink in Three-Phase Fault Analysis on Transmission line
 
Switch gear and protection
Switch gear and protectionSwitch gear and protection
Switch gear and protection
 
Protection & switchgear
Protection & switchgear  Protection & switchgear
Protection & switchgear
 
s.pdf
s.pdfs.pdf
s.pdf
 
Et601 chapter1 ayu
Et601  chapter1 ayuEt601  chapter1 ayu
Et601 chapter1 ayu
 
IRJET- Low Volatge Ride through Solution for Wind Energy Conversion System
IRJET- Low Volatge Ride through Solution for Wind Energy Conversion SystemIRJET- Low Volatge Ride through Solution for Wind Energy Conversion System
IRJET- Low Volatge Ride through Solution for Wind Energy Conversion System
 
Fault Calculation.pptx
Fault Calculation.pptxFault Calculation.pptx
Fault Calculation.pptx
 
Fy3610821086
Fy3610821086Fy3610821086
Fy3610821086
 
Tata steel UISL Power Quality final.pptx
Tata steel UISL Power Quality final.pptxTata steel UISL Power Quality final.pptx
Tata steel UISL Power Quality final.pptx
 
Power Swing Phenomena and Comparative Study of Its Detection on Transmission ...
Power Swing Phenomena and Comparative Study of Its Detection on Transmission ...Power Swing Phenomena and Comparative Study of Its Detection on Transmission ...
Power Swing Phenomena and Comparative Study of Its Detection on Transmission ...
 

Mais de vaibyfrndz (6)

paper presentaton topic on power theft prevention and quality improvement by ...
paper presentaton topic on power theft prevention and quality improvement by ...paper presentaton topic on power theft prevention and quality improvement by ...
paper presentaton topic on power theft prevention and quality improvement by ...
 
prevention of power theft and power uality by the help of fuzzy logic
prevention of power theft and power uality by the help of fuzzy logicprevention of power theft and power uality by the help of fuzzy logic
prevention of power theft and power uality by the help of fuzzy logic
 
kota super thermal power plant (kstps)
kota super thermal power plant (kstps)kota super thermal power plant (kstps)
kota super thermal power plant (kstps)
 
SOLAR POWERED THREE PHASE MOTOR FOR VARIOUS APPLICATION
SOLAR POWERED THREE PHASE MOTOR FOR VARIOUS APPLICATIONSOLAR POWERED THREE PHASE MOTOR FOR VARIOUS APPLICATION
SOLAR POWERED THREE PHASE MOTOR FOR VARIOUS APPLICATION
 
improvement of thrust force ripple in ultra high speed train
improvement of thrust force ripple in ultra high speed trainimprovement of thrust force ripple in ultra high speed train
improvement of thrust force ripple in ultra high speed train
 
harduaganj thermal power station h.t.p.s.
harduaganj thermal power station h.t.p.s.harduaganj thermal power station h.t.p.s.
harduaganj thermal power station h.t.p.s.
 

Último

Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
9953056974 Low Rate Call Girls In Saket, Delhi NCR
 
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
9953056974 Low Rate Call Girls In Saket, Delhi NCR
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
dollysharma2066
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.ppt
MsecMca
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
dharasingh5698
 
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
9953056974 Low Rate Call Girls In Saket, Delhi NCR
 

Último (20)

Unleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapUnleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leap
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
 
Design For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the startDesign For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the start
 
Double rodded leveling 1 pdf activity 01
Double rodded leveling 1 pdf activity 01Double rodded leveling 1 pdf activity 01
Double rodded leveling 1 pdf activity 01
 
data_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfdata_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdf
 
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
 
Unit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdfUnit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdf
 
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
 
Block diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptBlock diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.ppt
 
chapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineeringchapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineering
 
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performance
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.ppt
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . ppt
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
 
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
 
NFPA 5000 2024 standard .
NFPA 5000 2024 standard                                  .NFPA 5000 2024 standard                                  .
NFPA 5000 2024 standard .
 

CONCEPT OF SYMMETRICAL COMPONENT AS A TECHNIQUE FOR ANALYSIS OF FAULT AND IMPROVEMENT OF OVERCURRENT PROTECTION SCHEME

  • 1. A SEMINAR PRESENTATION ON “CONCEPT OF SYMMETRICAL COMPONENT AS A TECHNIQUE FOR ANALYSIS OF FAULT AND IMPROVEMENT OF OVERCURRENT PROTECTION SCHEME” Submitted to: Submitted by: Mr. Ankush Tandon Saurabh Varshney Mrs. Deepti Arela (10ESKEE106) 1
  • 2. CONTENT  INTRODUCTION  PROTECTION SYSTEM  SYMMETRICAL COMPONENT  FAULT  OVERCURRENT RELAY  ALGORITHM  SIMULATION DISTRIBUTION SYSTEM  RESULTS  CONCLUSION 2
  • 3. INTRODUCTION  Aim of my seminar topic is better understanding the concept of symmetrical components for enhancing protection scheme by providing a practical technology for understanding and analyzing power system operation during unbalanced condition. 3
  • 4. PROTECTION SYSTEM What is need of protective system ?  In order to maintain steady state of power system by taking correct and quick remedial action during any faulty condition. Properties of a good protective system Automatic Quick Minimum amount of disruption 4
  • 5. SYMMETRICAL COMPONENT  Unbalanced systems are difficult to handle.  It provide balanced analysis of an unbalanced system  The unbalanced three phase system can be transformed into three balanced phasors  Positive Sequence  Negative Sequence  Zero Sequence 5
  • 6. POSITIVE PHASE SEQUENCE  Each have the same magnitude.  Each positive sequence voltage or current quantity is displaced 120 from one another.  The positive sequence quantities have a-b-c, counter clock-wise, phase rotation. 6
  • 7. NEGATIVE PHASE SEQUENCE  Each have the same magnitude.  Each negative sequence voltage or current quantity is displaced 120 from one another.  The negative sequence quantities have a-c-b, counter clock-wise, phase rotation. 7
  • 8. ZERO PHASE SEQUENCE  Each zero sequence quantity has the same magnitude.  All three phasor with no angular displacement between them, all in phase. 8
  • 9. 9 FAULT o General Causes of fault  Fault due to lightning  Tree limbs falling on the line  Wind damage  Effects of fault  Flow of excessive current  Abnormal voltages  Induces over voltages on neighbouring equipments.  Hazards to human, equipment and animals
  • 10. TYPES OF FAULTS • Balanced Faults : – Three-phase fault • Unbalanced Faults : – Single line to ground fault – Line to line fault – Double line to ground fault 10
  • 12. SINGLE LINE TO GROUND FAULT  The most common type of fault is the single line to ground fault: 12
  • 13. 13  The SLG fault can be described by the following voltage and current relationship: Ib=0 & Ic=0 Va=IaZf  The Sequence current can be given as:
  • 14. LINE TO LINE FAULT  It occurs when two conductors are short circuited.  There is no zero sequence component due to absence of ground return path.  The positive and negative sequence components are connected in parallel. 14
  • 15. DOUBLE LINE TO GROUND FAULT  In double line to ground fault two line conductors come in contact with each other and ground .  The networks are connected in parallel.  For the zero sequence component it requires to add an external impedance of Zf+3Zg 15
  • 16. OVER CURRENT RELAY  Short-circuit currents are generally several times (5 to 20) full load current. Hence fast fault clearance is always desirable on short circuits.  A relay that operates or picks up when it’s current exceeds a predetermined value (setting value) is called Over current Relay.  Over current includes short-circuit protection, and short circuits can be:  Phase faults  Earth faults  Winding faults 16
  • 17. TYPES OF OVER CURRENT RELAY I. Instantaneous Over current (Definite Current) Relay II. Definite Time Over current Relay III. Inverse Time Over current Relay (IDMT Relay) i. Moderately Inverse ii. Very Inverse Time iii. Extremely Inverse IV. Directional over current Relay 17
  • 18. ALGORITHM  The criterion function for discriminating fault from non fault switching is defined as follows : R= |I1|-|I2| / |I1|+|I2| 18
  • 20. RESULTS Several non faults events are applied to this system along with some short circuit events a different time. The discrimination of fault from a non fault event could be done by representing two cases  Transformer energizing  Fault 20
  • 21. TRANSFORMER ENERGIZING  Various inrush current condition were simulated.  Various parameters which have considerable effect on the characteristic of the current signal were changed and was analysed. FAULT  In this case a single line to ground fault occurs. 21
  • 22. 22 NON FAULT CONDITION WHEN VALUE OF R>=.35s FAULTY CONDITION WHEN VALUE OF R<.35s
  • 23. 23 THREE PHASE CURRENT BEFORE FAULT THREE PHASE CURRENT AFTER FAULT
  • 24. CONCLUSION  Simple method of improving over current relays operation by algorithm, based on different behaviour of the current amplitudes. Based on the differences, a criterion function R is defined such that undesirable operation of the over current relays to the switching is prevented. 24