SlideShare uma empresa Scribd logo
1 de 18
Baixar para ler offline
Ref No:MEC:Dhaka:April:2022:18
PROPOSED FIRE SAFETY PLAN DRAWING
PROJECT NAME AND ADDRESS
DR. MD. ABDUL WAKIL
OWNER'S NAME
OCCUPANCY CLASSIFICATION
BUILDING TYPE
PREPARED BY
A2
R.C.C BUILDING
MART ENGINEERING & CONSULTANCY
HOTLINE:-01717-432054, 01670-212478
ENGR. M.A. RASHID TIPU,CFPS
Certified Fire Protection Specialist
Ba-08, South Badda, Gulshan, (Behind of shooting club)
Dhaka-1212, Bangladesh.
Mobile:-01717-432054, 01670-212478
APPROVED BY
DEPARTMENT OF
FIRE SERVICE & CIVIL DEFENSE
38-46, ROAD-KAZI-ALAUDDIN ROAD,
SIDDIQUE BAZAR, DHAKA 1000
FAISAL MAHBUB
IAB Membership & Rajuk Registration No-M-015
Cell: 01980001277
ARCHITECT :
AHMED YOUSUF HOSSAIN
HOUSE # 7, FLAT # C/2, ROAD-04.
GULSHAN # 1, DHAKA-1212
OWNER'S NAME :
WE KILL FIRE BEFORE IT KILLS YOU
CONSULTANT:
PROPOSED 16 - STORIED RESIDENTIAL BUILDING
AT PLOT NO-03, ROAD NO - 201, SECTOR NO-02,
UNITED CITY, MADANI AVENUE, SATARKUL, DHAKA.
CS DAG - 391, RS DAG - 233 & 234
MOUZA - SATARKUL, PS - BADDA, DHAKA.
LAYOUT DRAWING OF GROUND FLOOR
05
06
07
09
INDEX & LEGEND
00 TOP SHEET
01
02
03
04
08
LAYOUT DRAWING OF 1ST FLOOR
MASTER PLAN MASTER PLAN
10
POSITIVE SUCTION FIRE PUMP SCHEMATIC
DIAGRAM AND INSTALLATION DETAILING
FIRE ALARM RISER DIAGRAM
ELEVATION & SECTION VIEW
11
BUILDING AREA :
RESIDENTIAL & REFUGE AREA
LAYOUT DRAWING OF SUBSTATION
INSTRUCTIONS: SUB-STATION ROOM
ROOF FLOOR : PROPOSED LIGHTING PROTECTION SYSTEM (LPS).
13
PAGE NO. DRAWING TITLE DESCRIPTION
INDEX
12
GOOGLE MAP
FIRE PUMP ROOM, WATER RESERVOIR,PARKING AREA
14
FIRE CONTROL PANEL & 150 KVA SUBSTATION ROOM,
100 KVA GENERATOR & PARKING AREA
PROPOSED SINGLE LINE DIAGRAM (SLD)
15
COMMUNITY HALL
R. S MOUZA MAP
LAYOUT DRAWING OF 2ND TO 14TH FLOOR
LAYOUT DRAWING OF 8TH FLOOR
LAYOUT DRAWING OF 15TH FLOOR & ROOF FLOOR
RESIDENTIAL AREA
ROOF OF COMMON ROOM
16
PROJECT NAME & ADDRESS:
OWNER'S NAME / REPRESENTATIVE
PREPARED BY
ENGINEER
FIRE PROFESSIONAL
APPROVED BY
DEPARTMENT OF FIRE SERVICE
& CIVIL DEFENSE.
Head Office: 38-46, Road:
KaziAlauddin Road, Siddique Bazar, Dhaka.
SCALE
PAGE SIZE:
1:100
21-12-2021
A-3
DATE
CONSULTANT:
DESIGNER
ARCHITECT
PROPOSED 16 - STORIED RESIDENTIAL BUILDING
AT PLOT NO-03, ROAD NO - 201, SECTOR NO-02,
UNITED CITY, MADANI AVENUE, SATARKUL, DHAKA.
CS DAG - 391, RS DAG - 233 & 234
MOUZA - SATARKUL, PS - BADDA, DHAKA.
AHMED YOUSUF HOSSAIN
S/O - Mohammad Abdul Bari
MOTHERS NAME -Asiya Bari
House # 7, Flat # C/2, Road-04. Gulshan # 1,Dhaka-1212.
MART ENGINEERING & CONSULTANCY
Address: House -10,Road-03,(1st FL), Middle Badda, Gulshan
Badda Link ,Road, Dhaka-1212.
Mobile : +88017 - 17432054
PAGE NO : 01
Total area
01 1st Floor (Community) 122.26
Sl. No. Floor Total (Sqm)
14 15th Floor / Roof Floor 105.90
02 2nd Floor 223.27
03 3rd Floor
04 4th Floor
05 5th Floor
06 6th Floor
07 7th Floor
08 8th Floor
09 9th Floor
10 10th Floor
11 11th Floor
12 12th Floor
13 13th Floor
13 14th Floor
223.27
223.27
223.27
223.27
223.27
223.27
223.27
223.27
223.27
223.27
223.27
223.27
Ground floor 348.77
3479.44
TOTAL FLOOR AREA:
PROJECT NAME & ADDRESS:
OWNER'S NAME / REPRESENTATIVE
PREPARED BY
ENGINEER
FIRE PROFESSIONAL
APPROVED BY
DEPARTMENT OF FIRE SERVICE
& CIVIL DEFENSE.
Head Office: 38-46, Road:
KaziAlauddin Road, Siddique Bazar, Dhaka.
SCALE
PAGE SIZE:
1:100
21-12-2021
A-3
DATE
CONSULTANT:
DESIGNER
ARCHITECT
PROPOSED 16 - STORIED RESIDENTIAL BUILDING
AT PLOT NO-03, ROAD NO - 201, SECTOR NO-02,
UNITED CITY, MADANI AVENUE, SATARKUL, DHAKA.
CS DAG - 391, RS DAG - 233 & 234
MOUZA - SATARKUL, PS - BADDA, DHAKA.
AHMED YOUSUF HOSSAIN
S/O - Mohammad Abdul Bari
MOTHERS NAME -Asiya Bari
House # 7, Flat # C/2, Road-04. Gulshan # 1,Dhaka-1212.
MART ENGINEERING & CONSULTANCY
Address: House -10,Road-03,(1st FL), Middle Badda, Gulshan
Badda Link ,Road, Dhaka-1212.
Mobile : +88017 - 17432054
PAGE NO : 02
Google Map
PROJECT NAME & ADDRESS:
OWNER'S NAME / REPRESENTATIVE
PREPARED BY
ENGINEER
FIRE PROFESSIONAL
APPROVED BY
DEPARTMENT OF FIRE SERVICE
& CIVIL DEFENSE.
Head Office: 38-46, Road:
KaziAlauddin Road, Siddique Bazar, Dhaka.
SCALE
PAGE SIZE:
1:100
21-12-2021
A-3
DATE
CONSULTANT:
DESIGNER
ARCHITECT
PROPOSED 16 - STORIED RESIDENTIAL BUILDING
AT PLOT NO-03, ROAD NO - 201, SECTOR NO-02,
UNITED CITY, MADANI AVENUE, SATARKUL, DHAKA.
CS DAG - 391, RS DAG - 233 & 234
MOUZA - SATARKUL, PS - BADDA, DHAKA.
AHMED YOUSUF HOSSAIN
S/O - Mohammad Abdul Bari
MOTHERS NAME -Asiya Bari
House # 7, Flat # C/2, Road-04. Gulshan # 1,Dhaka-1212.
MART ENGINEERING & CONSULTANCY
Address: House -10,Road-03,(1st FL), Middle Badda, Gulshan
Badda Link ,Road, Dhaka-1212.
Mobile : +88017 - 17432054
PAGE NO : 04
1
8
.
2
9
m
W
I
D
E
R
O
A
D
19.65m
22.11m
2
0
.0
0
m
25.61m
FIRE STAIR
5.08mx2.00m
FIRE LIFT
1.96mx2.44m
GUARD
POST
2.38mx1.40m
E
N
T
R
Y
E
X
IT
GREEN
GREEN
GREEN
GREEN
GREEN
GREEN
3.16m
3.05m
SW
SEPTIC
TANK
TO SURFACE DRAIN
LT Panel
PROPOSED UNDER GROUND
FIRE WATER RESERVOIR
50,000 US GALLON
Switchgear room
10'-3X7'-3"
150KVA
Transformer
Room
100KVA
Generator Room
FHC
Standpipe Riser
& Drain Pipe
Fire Hose
Connection
Ø65mm
Landing
valve
FDC
Ø150mm
Pillar
Hydrant
2
WAY(65MM)
FIRE
DEPARTMENT
CONNECTION
Ø150mm
Underground Pipe
Fire Control
Room
PROPOSED 16 - STORIED
RESIDENTIAL BUILDING
STAIR
2.87mx4.27m
PROPOSED
FIRE PUMP ROOM
N
MASTER PLAN
SCALE :- 1 : 200
PROJECT NAME & ADDRESS:
OWNER'S NAME / REPRESENTATIVE
PREPARED BY
ENGINEER
FIRE PROFESSIONAL
APPROVED BY
DEPARTMENT OF FIRE SERVICE
& CIVIL DEFENSE.
Head Office: 38-46, Road:
KaziAlauddin Road, Siddique Bazar, Dhaka.
SCALE
PAGE SIZE:
1:100
21-12-2021
A-3
DATE
CONSULTANT:
DESIGNER
ARCHITECT
PROPOSED 16 - STORIED RESIDENTIAL BUILDING
AT PLOT NO-03, ROAD NO - 201, SECTOR NO-02,
UNITED CITY, MADANI AVENUE, SATARKUL, DHAKA.
CS DAG - 391, RS DAG - 233 & 234
MOUZA - SATARKUL, PS - BADDA, DHAKA.
AHMED YOUSUF HOSSAIN
S/O - Mohammad Abdul Bari
MOTHERS NAME -Asiya Bari
House # 7, Flat # C/2, Road-04. Gulshan # 1,Dhaka-1212.
MART ENGINEERING & CONSULTANCY
Address: House -10,Road-03,(1st FL), Middle Badda, Gulshan
Badda Link ,Road, Dhaka-1212.
Mobile : +88017 - 17432054
PAGE NO : 05
226
235
234
236
887
227
129
233
902
228
232
128
888 130
N
O
R. S MOUZA MAP
SCALE : 16" = 1 MILE
PROPOSED PLOT
PROJECT NAME & ADDRESS:
OWNER'S NAME / REPRESENTATIVE
PREPARED BY
ENGINEER
FIRE PROFESSIONAL
APPROVED BY
DEPARTMENT OF FIRE SERVICE
& CIVIL DEFENSE.
Head Office: 38-46, Road:
KaziAlauddin Road, Siddique Bazar, Dhaka.
SCALE
PAGE SIZE:
1:100
21-12-2021
A-3
DATE
CONSULTANT:
DESIGNER
ARCHITECT
PROPOSED 16 - STORIED RESIDENTIAL BUILDING
AT PLOT NO-03, ROAD NO - 201, SECTOR NO-02,
UNITED CITY, MADANI AVENUE, SATARKUL, DHAKA.
CS DAG - 391, RS DAG - 233 & 234
MOUZA - SATARKUL, PS - BADDA, DHAKA.
AHMED YOUSUF HOSSAIN
S/O - Mohammad Abdul Bari
MOTHERS NAME -Asiya Bari
House # 7, Flat # C/2, Road-04. Gulshan # 1,Dhaka-1212.
MART ENGINEERING & CONSULTANCY
Address: House -10,Road-03,(1st FL), Middle Badda, Gulshan
Badda Link ,Road, Dhaka-1212.
Mobile : +88017 - 17432054
PAGE NO : 03
1
8
.
2
9
m
W
I
D
E
R
O
A
D
19.65m
22.11m
2
0
.0
0
m
25.61m
FIRE STAIR
5.08mx2.00m
FIRE LIFT
1.96mx2.44m
LIFT
LOBBY
2.21mx1.57m
STAIR
2.87mx4.27m
LIFT
1.96mx1.52m
Level
+
0.76m
GUARD
POST
2.38mx1.40m
E
N
T
R
Y
E
X
IT
UP
GREEN
GREEN
GREEN
GREEN
GREEN
GREEN
TOILET
1.27mx2.29m
DRIVER'S
SITTING
1.40mx3.02m
D R I V E W A Y
3.16m
CAR
DROP
OFF
AREA
3.05m
UP
SW
SEPTIC
TANK
TO SURFACE DRAIN
SYMBOL SYMBOL NAME Q.T
03
Smoke Detector 07
Fire Alarm Control Panel 01
Horn With Light 06
Manual call points
P 03
SYMBOL SYMBOL NAME Q.T SYMBOL SYMBOL NAME Q.T
02
Fire Hose Connection Class- III 01
Fire Door 2 Rated 06
17
Sprinkler K- 11.2
FIRST AID BOX 04
Extinguisher (ABC & CO2) 07
ADDRESSABLE OUTPUT MODULE
ABC
CO2
SYMBOL SYMBOL NAME Q.T
02
02
03
03
FM 200 GAS Nozzle 360°
100 LETTER FM 200 GAS CYLINDER
A Actuator
P Pressure switch
FM-200 System Control Panel 02
Heat Detector
NOVEC-1230
FACP
FACP
POSITIVE AIR PRESSURIZED.
GROUND FLOOR: 150KVA SUB-STATION, 100KVA GENERATOR, FIRE CONTROL ROOM & FIRE PUMP ROOM
Floor Area:2000.04 sft
Scale : 1:100
FOAM
FACP
FM-200 System Control Panel
100 LETTER FM 200 FOAM CYLINDER
FM 200 FOAM Nozzle 360°
01
01
01
N
LT Panel
EXHAUST
SILENCER
PROPOSED UNDER GROUND
FIRE WATER RESERVOIR
50,000 US GALLON
UP
DN
P
500 GPM
ELECTRIC
PUMP
500 GPM
DIESEL
ENGINE
PUMP
10 GPM
JOCKEY
PUMP
P
Safety
Lobby
Safety Lobby
Fire Control Room
1.27mx1.52m
FACP
P
ABC
CO2
100
LETTER
CYLINDER
100
LETTER
CYLINDER
Switchgear room
10'-3X7'-3"
P A
Exit
Exit P A
NOVEC-1230
FACP ABC
CO2
150KVA
Transformer Room
9'-6''x9'-10''
Novec-1230 Gas Fire
Suppression System
ABC
CO2
FOAM
FACP
Exit
100
LETTER
FOAM
CYLINDER
100KVA
Generator
Room
7'-7''x15'-0''
Foam
Fire
Suppression
system
NOVEC-1230
FACP
ABC
CO2
ABC
CO2
ABC
CO2
ABC
CO2
ABC
CO2
FHC
Standpipe Riser
& Drain Pipe
Fire Hose
Connection
ABC
CO2
POSITIVE AIR
PRESSURIZED.
Ø65mm
Landing
valve
4 HOUR FIRE
RATED WALL
4 HOUR
RATED WALL
4 HOUR FIRE
RATED WALL
4 HOUR FIRE
RATED WALL
Sprinkler Head
Ø25mm
Ø25mm
Ø25mm
Ø25mm
Ø25mm
Ø32mm
Ø25mm
Ø25mm
Ø25mm
Ø25mm
Ø25mm
Ø25mm
Ø25mm
Ø25mm
Ø25mm
Ø32mm Ø50mm
Ø25mm
Ø25mm
Ø65mm Ø65mm Ø65mm
Ø65mm
Ø50mm
WF
AIM
AIM
To
Nearest
Drain
Pit
Zone
Control
Valve
P
A
AIM AIM AIM AIM AIM
AIM AIM AIM AIM AIM
FHC
AIM 12
SYMBOL SYMBOL NAME Q.T
00
Sprinkler K- 11.2
PILLAR HYDRANT 01
FIRST AID BOX 00
01
2 way(65mm) Fire Department Connection
FDC
PROJECT NAME & ADDRESS:
OWNER'S NAME / REPRESENTATIVE
PREPARED BY
ENGINEER
FIRE PROFESSIONAL
APPROVED BY
DEPARTMENT OF FIRE SERVICE
& CIVIL DEFENSE.
Head Office: 38-46, Road:
KaziAlauddin Road, Siddique Bazar, Dhaka.
SCALE
PAGE SIZE:
1:100
21-12-2021
A-3
DATE
CONSULTANT:
DESIGNER
ARCHITECT
PROPOSED 16 - STORIED RESIDENTIAL BUILDING
AT PLOT NO-03, ROAD NO - 201, SECTOR NO-02,
UNITED CITY, MADANI AVENUE, SATARKUL, DHAKA.
CS DAG - 391, RS DAG - 233 & 234
MOUZA - SATARKUL, PS - BADDA, DHAKA.
AHMED YOUSUF HOSSAIN
S/O - Mohammad Abdul Bari
MOTHERS NAME -Asiya Bari
House # 7, Flat # C/2, Road-04. Gulshan # 1,Dhaka-1212.
MART ENGINEERING & CONSULTANCY
Address: House -10,Road-03,(1st FL), Middle Badda, Gulshan
Badda Link ,Road, Dhaka-1212.
Mobile : +88017 - 17432054
PAGE NO : 06
INSTRUCTIONS: ELECTRICAL SUB STATION ROOM
PROJECT NAME & ADDRESS:
OWNER'S NAME / REPRESENTATIVE
PREPARED BY
ENGINEER
FIRE PROFESSIONAL
APPROVED BY
DEPARTMENT OF FIRE SERVICE
& CIVIL DEFENSE.
Head Office: 38-46, Road:
KaziAlauddin Road, Siddique Bazar, Dhaka.
SCALE
PAGE SIZE:
1:100
21-12-2021
A-3
DATE
CONSULTANT:
DESIGNER
ARCHITECT
PROPOSED 16 - STORIED RESIDENTIAL BUILDING
AT PLOT NO-03, ROAD NO - 201, SECTOR NO-02,
UNITED CITY, MADANI AVENUE, SATARKUL, DHAKA.
CS DAG - 391, RS DAG - 233 & 234
MOUZA - SATARKUL, PS - BADDA, DHAKA.
AHMED YOUSUF HOSSAIN
S/O - Mohammad Abdul Bari
MOTHERS NAME -Asiya Bari
House # 7, Flat # C/2, Road-04. Gulshan # 1,Dhaka-1212.
MART ENGINEERING & CONSULTANCY
Address: House -10,Road-03,(1st FL), Middle Badda, Gulshan
Badda Link ,Road, Dhaka-1212.
Mobile : +88017 - 17432054
PAGE NO : 07
LT Panel
HT
Panel
SYMBOL SYMBOL NAME Q.T
03
Heat Detector
Smoke Detector 03
ABORT SWITCH 03
Horn With Light 03
Manual call points
P 00
Actuator SWITCH 03
PRESSURE SWITCH 03
03
FIRST AID BOX
Fire Door 2 Rated 03
A
P
FM 200 GAS NOZZLE 360°
100 LETTER FM 200 GAS CYLINDER
FM-200 System Control Panel 01
Extinguisher (ABC & CO2) 5KG 03
4 HOUR RATED WALL
NOVEC-1230
FACP
02
02
FOAM NOZZLE 360°
FOAM
FACP
FOAM System Control Panel
100 LETTER FOAM CYLINDER
01
01
01
Floor Area: 320 sft
Scale : 1:100
ABC
CO2
AS PER
DRAWING
ABC
CO2
ABC
CO2
FOAM
FACP
Exit
100
LETTER
CYLINDER
100
LETTER
FOAM
CYLINDER
100
LETTER
CYLINDER
150KVA
Transformer Room
9'-6''x9'-10''
Novec-1230 Gas Fire
Suppression System
Switchgear room
10'-3X7'-3"
100KVA
Generator
Room
7'-7''x15'-0''
Foam
Fire
Suppression
system
P A
150 KVA Sub-Station, 100 KVA Generator
NOVEC 1230 FIRE SUPPRESSION SYSTEM
Exit
Exit P A
NOVEC-1230
FACP ABC
CO2
N
P
A
NOVEC-1230
FACP
11'-6"
8'-10"
15'-9"
10'-1"
5'-10"
7'-3"
1. Electric backup for fire Lift
2. Electric backup for Stair case Positive Air Pressure.
3. Electric backup Ventilation system with Cross fresh air
4. Electric backup Fire Pump/Jockey pump
5. All signes Including Backup Emergency Exit sing
Generator & Emergency power Generator Room
1. Separation Rating
2. Wall: 4 Hour, Door: 2 Hour Fire Rating
3. Suppression: Clean Agent
4. Capacity :100KVA
5. Location : Ground Floor
TRANSFORMER & SWITCHGEAR ROOM
1. Separation Rating
2. Wall: 4 Hour, Door: 2 Hour Fire Rating
3. Suppression: Clean Agent
4. Capacity : 150KVA
5. Location : Ground Floor
NOTE:
SCHEMATIC DRAWING FOR
AUTOMATIC CLEAN AGENT
DISTRBUTION SYSTEM FOR
SUBSTATION ROOM SIZE
APPROXIMATELY 220SFT
PROJECT NAME & ADDRESS:
OWNER'S NAME / REPRESENTATIVE
PREPARED BY
ENGINEER
FIRE PROFESSIONAL
APPROVED BY
DEPARTMENT OF FIRE SERVICE
& CIVIL DEFENSE.
Head Office: 38-46, Road:
KaziAlauddin Road, Siddique Bazar, Dhaka.
SCALE
PAGE SIZE:
1:100
21-12-2021
A-3
DATE
CONSULTANT:
DESIGNER
ARCHITECT
PROPOSED 16 - STORIED RESIDENTIAL BUILDING
AT PLOT NO-03, ROAD NO - 201, SECTOR NO-02,
UNITED CITY, MADANI AVENUE, SATARKUL, DHAKA.
CS DAG - 391, RS DAG - 233 & 234
MOUZA - SATARKUL, PS - BADDA, DHAKA.
AHMED YOUSUF HOSSAIN
S/O - Mohammad Abdul Bari
MOTHERS NAME -Asiya Bari
House # 7, Flat # C/2, Road-04. Gulshan # 1,Dhaka-1212.
MART ENGINEERING & CONSULTANCY
Address: House -10,Road-03,(1st FL), Middle Badda, Gulshan
Badda Link ,Road, Dhaka-1212.
Mobile : +88017 - 17432054
PAGE NO : 08
LIFT
LOBBY
1.68mx1.57m
TOILET
2.21mx1.30m
COMMUNITY HALL
7.76mx9.73m
ROOF
OF
ELECTRO-
MECHANICAL
ROOM
UP
DN
FIRE STAIR
5.08mx2.00m
STAIR
2.87mx4.27m
Safety
Lobby
Safety Lobby
FHC
Standpipe Riser
& Drain Pipe
Fire Hose
Connection
Ø65mm
Landing
valve
FIRE LIFT
1.96mx2.44m
LIFT
1.96mx1.52m
ABC
CO2
4 HOUR FIRE
RATED WALL
4 HOUR FIRE
RATED WALL
POSITIVE AIR
PRESSURIZED.
P
SYMBOL SYMBOL NAME Q.T
00
Smoke Detector
Fire Alarm Control Panel
Horn With Light
Manual call points
P
SYMBOL SYMBOL NAME Q.T SYMBOL SYMBOL NAME Q.T
Standpipe Riser & Drain Pipe 01
Fire Hose Connection Class- III
Fire Door 2 Rated
00
Sprinkler K- 11.2
PILLAR HYDRANT 01
FIRST AID BOX 00
Extinguisher (ABC & CO2)
00
01
2 way(65mm) Fire Department Connection
4 HOUR RATED WALL
ABC
CO2
Heat Detector
FDC
FACP
POSITIVE AIR PRESSURIZED.
1ST FLOOR: FACP ROOM & RESIDENTIAL AREA
Floor Area:122.26Sqm
Scale : 1:100
06
01
01
02
01
04
AS PER
DRAWING
01
N
FHC
PROJECT NAME & ADDRESS:
OWNER'S NAME / REPRESENTATIVE
PREPARED BY
ENGINEER
FIRE PROFESSIONAL
APPROVED BY
DEPARTMENT OF FIRE SERVICE
& CIVIL DEFENSE.
Head Office: 38-46, Road:
KaziAlauddin Road, Siddique Bazar, Dhaka.
SCALE
PAGE SIZE:
1:100
21-12-2021
A-3
DATE
CONSULTANT:
DESIGNER
ARCHITECT
PROPOSED 16 - STORIED RESIDENTIAL BUILDING
AT PLOT NO-03, ROAD NO - 201, SECTOR NO-02,
UNITED CITY, MADANI AVENUE, SATARKUL, DHAKA.
CS DAG - 391, RS DAG - 233 & 234
MOUZA - SATARKUL, PS - BADDA, DHAKA.
AHMED YOUSUF HOSSAIN
S/O - Mohammad Abdul Bari
MOTHERS NAME -Asiya Bari
House # 7, Flat # C/2, Road-04. Gulshan # 1,Dhaka-1212.
MART ENGINEERING & CONSULTANCY
Address: House -10,Road-03,(1st FL), Middle Badda, Gulshan
Badda Link ,Road, Dhaka-1212.
Mobile : +88017 - 17432054
PAGE NO : 09
LIVING
3.81mx4.95m
LIFT
1.96mx1.52m
FOYER
3.81mx1.96m
GUEST
BED
3.83mx4.37m
TOILET
2.58mx1.52m
PANTRY
1.68mx1.75m
ROOM
2.10mx1.57m
KITCHEN
2.63mx3.05m
TOILET
1.14mx1.40m
TOILET
2.58mx1.63m
TOILET
2.59mx1.91m
TOILET
2.21mx1.30m
BED-2
3.83mx4.67m
M.BED
4.17mx5.16m
F.LIVING
3.81mx3.33m
DINING
3.81mx4.93m
BALCONY
2.13mx1.02m
BALCONY
2.13mx2.03m
BALCONY
2.44mx1.10m
13.55m
18.08m
PLANTER
BOX
Front
Balcony
Excluded
FAR
and
Ground
Coverage
Other
balcony
excluded
FAR
but
included
ground
coverage
UP
DN
FIRE STAIR
5.08mx2.00m
STAIR
2.87mx4.27m
Safety
Lobby
Safety Lobby
ABC
CO2
FHC
Standpipe Riser
& Drain Pipe
Fire Hose
Connection
Ø65mm
Landing
valve
4 HOUR FIRE
RATED WALL
4 HOUR FIRE
RATED WALL
LIFT
LOBBY
1.68mx1.57m
FIRE LIFT
1.96mx2.44m
POSITIVE AIR
PRESSURIZED.
P
ABC
CO2
VER
1.27mx1.52m
KITCHEN MECHANICAL
VENTILATION SYSTEM
SYMBOL SYMBOL NAME Q.T
00X13=00
Smoke Detector
Fire Alarm Control Panel
Horn With Light
Manual call points
P
SYMBOL SYMBOL NAME Q.T SYMBOL SYMBOL NAME Q.T
Standpipe Riser & Drain Pipe 01
Fire Hose Connection Class- III
Fire Door 2 Rated
00
Sprinkler K- 11.2
PILLAR HYDRANT 00
FIRST AID BOX 13
Extinguisher (ABC & CO2)
00
00
2 way(65mm) Fire Department Connection
4 HOUR RATED WALL
ABC
CO2
Heat Detector
FDC
FACP
POSITIVE AIR PRESSURIZED.
2ND FLOOR TO 14TH (TYPICAL) FLOOR: RESIDENTIAL AREA
Floor Area: 223.27X13
=12,902.51 SQM
Scale : 1:100
03X13=39
01X13=13
01X13=13
02X13=26
AS PER
DRAWING
N
01X13=13
FHC 01X13=13
03X13=39
17.45m
PROJECT NAME & ADDRESS:
OWNER'S NAME / REPRESENTATIVE
PREPARED BY
ENGINEER
FIRE PROFESSIONAL
APPROVED BY
DEPARTMENT OF FIRE SERVICE
& CIVIL DEFENSE.
Head Office: 38-46, Road:
KaziAlauddin Road, Siddique Bazar, Dhaka.
SCALE
PAGE SIZE:
1:100
21-12-2021
A-3
DATE
CONSULTANT:
DESIGNER
ARCHITECT
PROPOSED 16 - STORIED RESIDENTIAL BUILDING
AT PLOT NO-03, ROAD NO - 201, SECTOR NO-02,
UNITED CITY, MADANI AVENUE, SATARKUL, DHAKA.
CS DAG - 391, RS DAG - 233 & 234
MOUZA - SATARKUL, PS - BADDA, DHAKA.
AHMED YOUSUF HOSSAIN
S/O - Mohammad Abdul Bari
MOTHERS NAME -Asiya Bari
House # 7, Flat # C/2, Road-04. Gulshan # 1,Dhaka-1212.
MART ENGINEERING & CONSULTANCY
Address: House -10,Road-03,(1st FL), Middle Badda, Gulshan
Badda Link ,Road, Dhaka-1212.
Mobile : +88017 - 17432054
PAGE NO : 10
LIVING
3.81mx4.95m
LIFT
1.96mx1.52m
FOYER
3.81mx1.96m
GUEST
BED
3.83mx4.37m
TOILET
2.58mx1.52m
PANTRY
1.68mx1.75m
ROOM
2.10mx1.57m
KITCHEN
2.63mx3.05m
TOILET
1.14mx1.40m
TOILET
2.58mx1.63m
TOILET
2.59mx1.91m
TOILET
2.21mx1.30m
BED-2
3.83mx4.67m
M.BED
4.17mx5.16m
F.LIVING
3.81mx3.33m
DINING
3.81mx4.93m
BALCONY
2.13mx1.02m
BALCONY
2.13mx2.03m
BALCONY
2.44mx1.10m
13.55m
18.08m
PLANTER
BOX
Front
Balcony
Excluded
FAR
and
Ground
Coverage
Other
balcony
excluded
FAR
but
included
ground
coverage
UP
DN
FIRE STAIR
5.08mx2.00m
STAIR
2.87mx4.27m
Safety
Lobby
Safety Lobby
ABC
CO2
FHC
Standpipe Riser
& Drain Pipe
Fire Hose
Connection
Ø65mm
Landing
valve
4 HOUR FIRE
RATED WALL
4 HOUR FIRE
RATED WALL
LIFT
LOBBY
1.68mx1.57m
FIRE LIFT
1.96mx2.44m
POSITIVE AIR
PRESSURIZED.
P
ABC
CO2
VER
1.27mx1.52m
KITCHEN MECHANICAL
VENTILATION SYSTEM
SYMBOL SYMBOL NAME Q.T
00
Smoke Detector
Fire Alarm Control Panel
Horn With Light
Manual call points
P
SYMBOL SYMBOL NAME Q.T SYMBOL SYMBOL NAME Q.T
Standpipe Riser & Drain Pipe 01
Fire Hose Connection Class- III
Fire Door 2 Rated
00
Sprinkler K- 11.2
PILLAR HYDRANT 00
FIRST AID BOX 01
Extinguisher (ABC & CO2)
00
00
2 way(65mm) Fire Department Connection
4 HOUR RATED WALL
ABC
CO2
Heat Detector
FDC
FACP
POSITIVE AIR PRESSURIZED.
8TH FLOOR: RESIDENTIAL & REFUGE AREA
Floor Area: 223.27X13
=12,902.51 SQM
Scale : 1:100
04
01
02
02
AS PER
DRAWING
N 01
FHC 01
04
17.45m
REFUGE AREA
PROJECT NAME & ADDRESS:
OWNER'S NAME / REPRESENTATIVE
PREPARED BY
ENGINEER
FIRE PROFESSIONAL
APPROVED BY
DEPARTMENT OF FIRE SERVICE
& CIVIL DEFENSE.
Head Office: 38-46, Road:
KaziAlauddin Road, Siddique Bazar, Dhaka.
SCALE
PAGE SIZE:
1:100
21-12-2021
A-3
DATE
CONSULTANT:
DESIGNER
ARCHITECT
PROPOSED 16 - STORIED RESIDENTIAL BUILDING
AT PLOT NO-03, ROAD NO - 201, SECTOR NO-02,
UNITED CITY, MADANI AVENUE, SATARKUL, DHAKA.
CS DAG - 391, RS DAG - 233 & 234
MOUZA - SATARKUL, PS - BADDA, DHAKA.
AHMED YOUSUF HOSSAIN
S/O - Mohammad Abdul Bari
MOTHERS NAME -Asiya Bari
House # 7, Flat # C/2, Road-04. Gulshan # 1,Dhaka-1212.
MART ENGINEERING & CONSULTANCY
Address: House -10,Road-03,(1st FL), Middle Badda, Gulshan
Badda Link ,Road, Dhaka-1212.
Mobile : +88017 - 17432054
PAGE NO : 11
LIFT
MACHINE ROOM
1.96mx6.05m
4.16m
1.09m
13.55m
1.85m
7.04m
2.90m
7.52m
13.55m
8.23m
2.67m
3.81m
4.50m
COMMON ROOM
7.76mx7.21m
9.86m
Raised 1.75m
Raised 1.75m
DN
1.78m
DN
TOILET
2.73mx1.27m
FIRE STAIR
5.08mx2.00m
STAIR
2.87mx4.27m
Safety
Lobby
Safety Lobby
ABC
CO2
FHC
Standpipe Riser
& Drain Pipe
Fire Hose
Connection
Ø65mm
Landing
valve
4 HOUR
RATED WALL
4 HOUR FIRE
RATED WALL
P
POSITIVE AIR
PRESSURIZED.
R
O
O
F
W
A
T
E
R
D
R
A
I
N
A
G
E
SLOPE
1:200
R
O
O
F
W
A
T
E
R
D
R
A
I
N
A
G
E
S
L
O
P
E
1
:
2
0
0
R
O
O
F
W
A
T
E
R
D
R
A
I
N
A
G
E
S
L
O
P
E
1
:
2
0
0
R
O
O
F
W
A
T
E
R
D
R
A
I
N
A
G
E
S
L
O
P
E
1
:
2
0
0
OPEN SKY
SYMBOL SYMBOL NAME Q.T
00
Smoke Detector
Fire Alarm Control Panel
Horn With Light
Manual call points
P
SYMBOL SYMBOL NAME Q.T SYMBOL SYMBOL NAME Q.T
Standpipe Riser & Drain Pipe 01
Fire Hose Connection Class- III
Fire Door 2 Rated
01
Class-I Hose Connection
PILLAR HYDRANT 00
FIRST AID BOX 01
Extinguisher (ABC & CO2)
00
00
2 way(65mm) Fire Department Connection
4 HOUR RATED WALL
ABC
CO2
Heat Detector
FDC
FACP
POSITIVE AIR PRESSURIZED.
15TH FLOOR & ROOF FLOOR: RESIDENTIAL AREA
Floor Area:105.90 SQM
Scale : 1:100
08
02
03
02
01
03
AS PER
DRAWING
02
ABC
CO2
ABC
CO2
P
FHC
N
PROJECT NAME & ADDRESS:
OWNER'S NAME / REPRESENTATIVE
PREPARED BY
ENGINEER
FIRE PROFESSIONAL
APPROVED BY
DEPARTMENT OF FIRE SERVICE
& CIVIL DEFENSE.
Head Office: 38-46, Road:
KaziAlauddin Road, Siddique Bazar, Dhaka.
SCALE
PAGE SIZE:
1:100
21-12-2021
A-3
DATE
CONSULTANT:
DESIGNER
ARCHITECT
PROPOSED 16 - STORIED RESIDENTIAL BUILDING
AT PLOT NO-03, ROAD NO - 201, SECTOR NO-02,
UNITED CITY, MADANI AVENUE, SATARKUL, DHAKA.
CS DAG - 391, RS DAG - 233 & 234
MOUZA - SATARKUL, PS - BADDA, DHAKA.
AHMED YOUSUF HOSSAIN
S/O - Mohammad Abdul Bari
MOTHERS NAME -Asiya Bari
House # 7, Flat # C/2, Road-04. Gulshan # 1,Dhaka-1212.
MART ENGINEERING & CONSULTANCY
Address: House -10,Road-03,(1st FL), Middle Badda, Gulshan
Badda Link ,Road, Dhaka-1212.
Mobile : +88017 - 17432054
PAGE NO : 12
ROOF OF STAIR
& O. H. W. R.
20000 LITTER
ROOF OF COMMON ROOM
ROOF OF LIFT
MACHINE ROOM
ROOF
OF
FIRE
STAIR
OPEN SKY
10'
8'
Grounding Electrode
No:01
Grounding Electrode (Size: Dia12.7mm)
Bounding Conductor (Width
12.7mm & Thickness 1.30mm)
Down Conductor-01
Size: 12mm Dia Copper Rod
10'
8'
Grounding Electrode
No:02
Grounding Electrode (Size: Dia12.7mm)
Bounding Conductor (Width
12.7mm & Thickness 1.30mm)
Down Conductor-01
Size: 12mm Dia Copper Rod
10'
8'
Grounding Electrode
No:04
Grounding Electrode (Size: Dia12.7mm)
Bounding Conductor (Width
12.7mm & Thickness 1.30mm)
Down Conductor-01
Size: 12mm Dia Copper Rod
10'
8'
Grounding Electrode
No:03
Grounding Electrode (Size: Dia12.7mm)
Bounding Conductor (Width
12.7mm & Thickness 1.30mm)
Down Conductor-01
Size: 12mm Dia Copper Rod
Roof Floor : Proposed Lighting Protection System (LPS).
LEGEND
Down Conductor (Solid
Rod ɸ-12mm Copper)
Bounding Conductor
(Solid or Standard
ɸ-17AWG Copper)
Earth Symbol
Earthing Rod (ɸ-12mm
Copper)
Air Terminal (ɸ-12mm
Copper) In The Periphery
top of the Building, Hight
2ft.
Calculation of Down Conductor,
DC = Total Periphery/100
= 569'/100
= 5.69
= 06 Pcs
Required Materials Calss-II
Follow Standard- NFPA780
Air Terminal Top
(ɸ-12mm Copper) In The
Periphery top of the
Building, Hight 2ft.
PROJECT NAME & ADDRESS:
OWNER'S NAME / REPRESENTATIVE
PREPARED BY
ENGINEER
FIRE PROFESSIONAL
APPROVED BY
DEPARTMENT OF FIRE SERVICE
& CIVIL DEFENSE.
Head Office: 38-46, Road:
KaziAlauddin Road, Siddique Bazar, Dhaka.
SCALE
PAGE SIZE:
1:100
21-12-2021
A-3
DATE
CONSULTANT:
DESIGNER
ARCHITECT
PROPOSED 16 - STORIED RESIDENTIAL BUILDING
AT PLOT NO-03, ROAD NO - 201, SECTOR NO-02,
UNITED CITY, MADANI AVENUE, SATARKUL, DHAKA.
CS DAG - 391, RS DAG - 233 & 234
MOUZA - SATARKUL, PS - BADDA, DHAKA.
AHMED YOUSUF HOSSAIN
S/O - Mohammad Abdul Bari
MOTHERS NAME -Asiya Bari
House # 7, Flat # C/2, Road-04. Gulshan # 1,Dhaka-1212.
MART ENGINEERING & CONSULTANCY
Address: House -10,Road-03,(1st FL), Middle Badda, Gulshan
Badda Link ,Road, Dhaka-1212.
Mobile : +88017 - 17432054
PAGE NO : 13
1.75m
1.25m
3.00m
NORTH ELEVATION
SCALE : 1 : 100
LIGHTNING ARRESTOR.
SECURITY LIGHT
ROAD LEVEL ± 00
2ND FLOOR LEVEL+ 7.32m
3RD FLOOR LEVEL+ 10.36m
5TH FLOOR LEVEL + 16.46m
4TH FLOOR LEVEL + 13.41m
PARAPET TOP + 48.46m
1ST FLOOR LEVEL +4.27m
O.H.W.T. TOP + 51.94m
PLINTH LEVEL + 0.91m
6TH FLOOR LEVEL + 19.51m
7TH FLOOR LEVEL + 22.56m
8TH FLOOR LEVEL + 25.60m
9TH FLOOR LEVEL + 28.65m
10TH FLOOR LEVEL + 31.70m
11TH FLOOR LEVEL + 34.75m
12TH FLOOR LEVEL + 37.80m
13TH FLOOR LEVEL + 40.84m
14TH FLOOR LEVEL + 43.89m
15TH FLOOR LEVEL + 46.94m
O.H.W.T
LEVEL + 0.76m
1.75m
1.25m
3.00m
LEVEL + 0.91m
0.91m
0.91m
0.91m
0.91m
0.91m
0.91m
0.91m
0.91m
0.91m
0.91m
0.91m
0.91m
0.91m
0.91m
0.91m
0.91m
0.91m
0.91m
0.91m
0.91m
0.91m
0.91m
0.91m
0.91m
0.91m
0.91m
0.91m
0.91m
0.91m
0.91m
3.05m
3.51m
3.05m
3.05m
3.05m
3.05m
3.05m
3.05m
3.05m
3.05m
3.05m
3.05m
3.05m
3.05m
3.05m
3.05m
3.05m
1.96m
51.94m
SECTION A-A
SCALE : 1 : 100
ROAD LEVEL ± 00
2ND FLOOR LEVEL+ 7.32m
3RD FLOOR LEVEL+ 10.36m
5TH FLOOR LEVEL + 16.46m
4TH FLOOR LEVEL + 13.41m
PARAPET TOP + 48.46m
1ST FLOOR LEVEL +4.27m
O.H.W.T. TOP + 51.94m
PLINTH LEVEL + 0.91m
6TH FLOOR LEVEL + 19.51m
7TH FLOOR LEVEL + 22.56m
8TH FLOOR LEVEL + 25.60m
9TH FLOOR LEVEL + 28.65m
10TH FLOOR LEVEL + 31.70m
11TH FLOOR LEVEL + 34.75m
12TH FLOOR LEVEL + 37.80m
13TH FLOOR LEVEL + 40.84m
14TH FLOOR LEVEL + 43.89m
15TH FLOOR LEVEL + 46.94m
LIGHTNING ARRESTOR.
SECURITY LIGHT
ELEVATION & SECTION VIEW
PROJECT NAME & ADDRESS:
OWNER'S NAME / REPRESENTATIVE
PREPARED BY
ENGINEER
FIRE PROFESSIONAL
APPROVED BY
DEPARTMENT OF FIRE SERVICE
& CIVIL DEFENSE.
Head Office: 38-46, Road:
KaziAlauddin Road, Siddique Bazar, Dhaka.
SCALE
PAGE SIZE:
1:100
21-12-2021
A-3
DATE
CONSULTANT:
DESIGNER
ARCHITECT
PROPOSED 16 - STORIED RESIDENTIAL BUILDING
AT PLOT NO-03, ROAD NO - 201, SECTOR NO-02,
UNITED CITY, MADANI AVENUE, SATARKUL, DHAKA.
CS DAG - 391, RS DAG - 233 & 234
MOUZA - SATARKUL, PS - BADDA, DHAKA.
AHMED YOUSUF HOSSAIN
S/O - Mohammad Abdul Bari
MOTHERS NAME -Asiya Bari
House # 7, Flat # C/2, Road-04. Gulshan # 1,Dhaka-1212.
MART ENGINEERING & CONSULTANCY
Address: House -10,Road-03,(1st FL), Middle Badda, Gulshan
Badda Link ,Road, Dhaka-1212.
Mobile : +88017 - 17432054
PAGE NO : 14
+10'-0"
1'-8"
Delivery
Pipe
,
Ø
125
mm
Delivery
Pipe
,
Ø
50
mm
Delivery
Pipe
,
Ø
125
mm
Ø150 mm
Header Pipe
Level (-) 3'-0"
Ø125 mm Suction for Engine Driven Fire Pump, Level (-)
12'-0"
Ø65 mm Suction for Motor Driven Jockey Pump, Level (-)
12'-0"
Ø125 mm Suction for Motor Driven Fire Pump, Level (-) 12'-0"
P SITIVE SUCTI N FIRE PUMP SCHEM TIC
DI GR M ND INST LL TI N DET ILING
Ø125mm Relief valve discharge Pipe,
Level (+) 0'-6"
Ø150mm Delivery Pipe,
Level (-) 3'-0"
64'-1"
Ø150mm Pipe from Deep Tubewell
to Fill the Underground
Water Reservore,
Level (-) 1'-0"
Level (-) 0'-0"
Level (+) 0'-0"
Water Level (-) 1'-0"
32'-4"
TS
TS
TS
Water Level Gauge
Ø150mm Pipe
WF
TS
10'-0"
Ø125mm Test Header
Pipe, Level (+) 0'-6"
Ø150mm Flow Meter
Pipe, Level (+) 0'-6"
WF
Ø50mm Drain Pipe
To Nearest Drain Pit
AIM
AIM Ø150mm
Standpipe Riser-01
Class-III Hose
Connection
Ø65mm
Branch Pipe
Proposed Fire Pump Schedule (Brand: , ......)
Type of Pump
Type of Driver
Rated Capacity (US GPM)
Rated Pressure (bar.g)
Rated Head (FT.)
M
a
i
n
F
i
r
e
P
u
m
p
(
E
P
) Stand By Fire Pump (DP) Jockey Pump (JP)
500.00
Horizontal Spilt Case
Centifugal
Vertical Multi-stage
Centifugal
Electrical Motor Diesel Engine Electrical Motor
100.00
10.00
Horizontal Spilt Case
Centifugal
Pump RPM 2900
500.00
100.00
10.00
2900
25.00
110.00
11.0
3000
Class- I Landing valve (Ø65mm Landing Valve)
Standpipe Riser & Drain Pipe
Pillar Hydrant
(2xØ65mm/Ø150mm)
Four Way Fire Department Connection
(4xØ65mm/Ø150mm)
LEGEND
S MB L S MB L N ME T
00
14
01
01
01
Class - III Hose Connection
(Ø40mm Pressure Hydrant Valve with Ø38mm
Canvas Hose & Ø38mm Variable Nozzle & Within Cabinate)
FIRE DEPARTMENT
CONNECTION -
2 WAY(65MM)
NON RETURN
VALVE: 100MM
Pillar Hydrant
AIR RELIFE VALVE
PRESSURE GAUGE
BALL VALVE
BALL VALVE
Ø150mm
Standpipe Riser-01
FDC
L
+10'-0"
Ø65mm
Branch Pipe
N TO L
Class-III Hose
Connection
Ø65mm
Branch Pipe
ROO L
FDC
Ø40mm
Branch Pipe
Ø40mm
Branch Pipe
PROPOSED UNDER GROUND
WATER RESERVOIR
60,000 US GALLON
Class-III Hose
Connection
Ø65mm
Branch Pipe
Ø40mm
Branch Pipe
ROUN L
+10'-0"
Ø65mm
Branch Pipe
Class-III Hose
Connection
Ø65mm
Branch Pipe
Ø40mm
Branch Pipe
Ø50mm
Pipe
W
F
AIM
AIM
To Nearest
Drain Pit
Zone Control
Valve Sprinkler
Ø150mm
Cross main
HOSE NOZZE
SPRING LOCK
HANDLE
1½" Ø CANVASS HOSE
2½" Ø LANDING VALVE
FIRE HOSE CABINET
(2'-4"X10"X2'-8")
WIRRED GLASS
1½" Ø CONTROLLED
PRESSURE HYDRNT
VALVE
6"
Ø
STANDPIPE
RISER
BALL VALVE
2½" Ø M.S. PIPE
PROJECT NAME & ADDRESS:
OWNER'S NAME / REPRESENTATIVE
PREPARED BY
ENGINEER
FIRE PROFESSIONAL
APPROVED BY
DEPARTMENT OF FIRE SERVICE
& CIVIL DEFENSE.
Head Office: 38-46, Road:
KaziAlauddin Road, Siddique Bazar, Dhaka.
SCALE
PAGE SIZE:
1:100
21-12-2021
A-3
DATE
CONSULTANT:
DESIGNER
ARCHITECT
PROPOSED 16 - STORIED RESIDENTIAL BUILDING
AT PLOT NO-03, ROAD NO - 201, SECTOR NO-02,
UNITED CITY, MADANI AVENUE, SATARKUL, DHAKA.
CS DAG - 391, RS DAG - 233 & 234
MOUZA - SATARKUL, PS - BADDA, DHAKA.
AHMED YOUSUF HOSSAIN
S/O - Mohammad Abdul Bari
MOTHERS NAME -Asiya Bari
House # 7, Flat # C/2, Road-04. Gulshan # 1,Dhaka-1212.
MART ENGINEERING & CONSULTANCY
Address: House -10,Road-03,(1st FL), Middle Badda, Gulshan
Badda Link ,Road, Dhaka-1212.
Mobile : +88017 - 17432054
PAGE NO : 15
SYMBOL
LEGEND WITH SPECIFICATION
SYMBOL NAME
Horn With Light
Smoke Detector
Heat Detector
Malti Detector Addressable
Manual call points
Addressable Fire Alarm Control Panel
Addressable Output Module
P
Addressable Input Module
AOM
AIM
SYMBOL SYMBOL NAME
03
06
00
22
Q.T
19
00
12
Q.T
AIM AIM AIM AIM AIM
AIM AIM AIM AIM AIM
MAIN FIRE ALARM CONTROL PANEL, No-01
2 LOOPS
BATTERY CAPACITY = 10 AH
SECURITY ROOM (GF)
AUX-ILIARY
POWER
SUPPLY
(NAC
CIRCUIT)
SOFTWARE INTERFACE WITH BMS SYSTEM
INTERFACE WITH PUBLIC ADDRESS
3 x 2.5rm wire from
primary power source
LOOP 2 LOOP 1
EOLR
FIRE ALARM RISER DIAGRAM
P
P
P
P P
P
P P
P
P
P
P
P P
P
P
P
EOLR
FACP
PROJECT NAME & ADDRESS:
OWNER'S NAME / REPRESENTATIVE
PREPARED BY
ENGINEER
FIRE PROFESSIONAL
APPROVED BY
DEPARTMENT OF FIRE SERVICE
& CIVIL DEFENSE.
Head Office: 38-46, Road:
KaziAlauddin Road, Siddique Bazar, Dhaka.
SCALE
PAGE SIZE:
1:100
21-12-2021
A-3
DATE
CONSULTANT:
DESIGNER
ARCHITECT
PROPOSED 16 - STORIED RESIDENTIAL BUILDING
AT PLOT NO-03, ROAD NO - 201, SECTOR NO-02,
UNITED CITY, MADANI AVENUE, SATARKUL, DHAKA.
CS DAG - 391, RS DAG - 233 & 234
MOUZA - SATARKUL, PS - BADDA, DHAKA.
AHMED YOUSUF HOSSAIN
S/O - Mohammad Abdul Bari
MOTHERS NAME -Asiya Bari
House # 7, Flat # C/2, Road-04. Gulshan # 1,Dhaka-1212.
MART ENGINEERING & CONSULTANCY
Address: House -10,Road-03,(1st FL), Middle Badda, Gulshan
Badda Link ,Road, Dhaka-1212.
Mobile : +88017 - 17432054
PAGE NO : 16
REB SUPPLY
M METER
11KV DROP OUT FUSE(100A)
11 KV LIGHTNING ARRESTER
G
12.7mm Dia Cu Conductor
(Body Earthing)
Earth Pit-9
Earth
Pit-8
Earth
Pit-7
12.7mm Dia Cu Conductor
12.7mm Dia Cu Conductor
100KVA Diesel Generator
440V, 50Hz, Prime-220KVA,
Standby-200KVA
12.7mm Dia Cu Conductor
12.7mm Dia Cu Conductor
12.7mm Dia Cu Conductor
12.7mm Dia Cu Conductor
EARTH PIT-6
EARTH PIT-5
EARTH PIT-4
EARTH PIT-3
(Neutral Earthing)
(Neutral Earthing)
(Body Earthing)
(Body Earthing)
100A ATS Panel
(Body Earthing)
150KVA TRANSFORMER
11KV / 415V,
Dyn11, 50Hz, Step Down.
%Z=6, OIL TYPE
1CX4X400RM NYY CABLE(TP+N)
630A TP MCCB
Adj-1
LT Panel
Load=497kw
Diversity Factor-40%
(Load=199KW)
3X50RM (NYSEYFGbY) HT CABLE
1CX4X150RM NYY CABLE(TP+N)
1CX4X150RM NYY CABLE(TP+N)
(Neutral Earthing)
PROPOSED SINGLE LINE DIAGRAM (SLD)
90KVAR
Door ECC=1X4.0 rm
CKT-
00
1CX4XX50
Sqmm
(TP+N)
NYY
ECC-
1CX1X25
Sqmm
BYA
CKT-
1
CKT-
2
CKT-
3
CKT-
4
CKT-
5
CKT-
6
CKT-
7
CKT-
8
CKT-
9
CKT-
10
CKT-
11
CKT-
12
CKT-
13
CKT-
14
Earth
Pit-10
12.7mm
Dia
Cu
Conductor
(Body Earthing)
Bus Bar- 372A (TP+N) & ECC- 186A, 30mmX8mm (TP+N) CU BUS BAR +20mmX6mm ECC
150A
TP
MCCB
CKT-
15
CKT-
16
CKT-
17
CKT-
18
CKT-
19
CKT-
20
CKT-
21
CKT-
22
CKT-
23
CKT-
24
CKT-
25
40A
DP
MCB
1CX2X10
Sqmm
(SP+N)
BYA
ECC
1CX1X6
Sqmm
BYA
40A
DP
MCB
1CX2X10
Sqmm
(SP+N)
BYA
ECC
1CX1X6
Sqmm
BYA
40A
DP
MCB
1CX2X10
Sqmm
(SP+N)
BYA
ECC
1CX1X6
Sqmm
BYA
40A
DP
MCB
1CX2X10
Sqmm
(SP+N)
BYA
ECC
1CX1X6
Sqmm
BYA
40A
DP
MCB
1CX2X10
Sqmm
(SP+N)
BYA
ECC
1CX1X6
Sqmm
BYA
40A
DP
MCB
1CX2X10
Sqmm
(SP+N)
BYA
ECC
1CX1X6
Sqmm
BYA
40A
DP
MCB
1CX2X10
Sqmm
(SP+N)
BYA
ECC
1CX1X6
Sqmm
BYA
40A
DP
MCB
1CX2X10
Sqmm
(SP+N)
BYA
ECC
1CX1X6
Sqmm
BYA
40A
DP
MCB
1CX2X10
Sqmm
(SP+N)
BYA
ECC
1CX1X6
Sqmm
BYA
40A
DP
MCB
1CX2X10
Sqmm
(SP+N)
BYA
ECC
1CX1X6
Sqmm
BYA
40A
DP
MCB
1CX2X10
Sqmm
(SP+N)
BYA
ECC
1CX1X6
Sqmm
BYA
40A
DP
MCB
1CX2X10
Sqmm
(SP+N)
BYA
ECC
1CX1X6
Sqmm
BYA
40A
DP
MCB
1CX2X10
Sqmm
(SP+N)
BYA
ECC
1CX1X6
Sqmm
BYA
40A
DP
MCB
1CX2X10
Sqmm
(SP+N)
BYA
ECC
1CX1X6
Sqmm
BYA
40A
DP
MCB
1CX2X10
Sqmm
(SP+N)
BYA
ECC
1CX1X6
Sqmm
BYA
40A
DP
MCB
1CX2X10
Sqmm
(SP+N)
BYA
ECC
1CX1X6
Sqmm
BYA
40A
DP
MCB
1CX2X10
Sqmm
(SP+N)
BYA
ECC
1CX1X6
Sqmm
BYA
40A
DP
MCB
1CX2X10
Sqmm
(SP+N)
BYA
ECC
1CX1X6
Sqmm
BYA
40A
DP
MCB
1CX2X10
Sqmm
(SP+N)
BYA
ECC
1CX1X6
Sqmm
BYA
40A
DP
MCB
1CX2X10
Sqmm
(SP+N)
BYA
ECC
1CX1X6
Sqmm
BYA
40A
DP
MCB
1CX2X10
Sqmm
(SP+N)
BYA
ECC
1CX1X6
Sqmm
BYA
40A
DP
MCB
1CX2X10
Sqmm
(SP+N)
BYA
ECC
1CX1X6
Sqmm
BYA
40A
DP
MCB
1CX2X10
Sqmm
(SP+N)
BYA
ECC
1CX1X6
Sqmm
BYA
40A
DP
MCB
1CX2X10
Sqmm
(SP+N)
BYA
ECC
1CX1X6
Sqmm
BYA
40A
DP
MCB
1CX2X10
Sqmm
(SP+N)
BYA
ECC
1CX1X6
Sqmm
BYA
40A
DP
MCB
1CX2X10
Sqmm
(SP+N)
BYA
ECC
1CX1X6
Sqmm
BYA
CKT-
26
CKT-
27
CKT-
28
CKT-
29
CKT-
30
40A
DP
MCB
1CX2X10
Sqmm
(SP+N)
BYA
ECC
1CX1X6
Sqmm
BYA
CKT-
31
40A
DP
MCB
1CX2X10
Sqmm
(SP+N)
BYA
ECC
1CX1X6
Sqmm
BYA
CKT-
32
40A
DP
MCB
1CX2X10
Sqmm
(SP+N)
BYA
ECC
1CX1X6
Sqmm
BYA
CKT-
33
DB-1
1ST
F
UNIT-A
Load=7KW
Diversity
Factor-40%
(Load=2.8KW)
DB-2
2ND
F
UNIT-A
Load=7KW
Diversity
Factor-40%
(Load=2.8KW)
DB-3
3RD
F
UNIT-A
Load=7KW
Diversity
Factor-40%
(Load=2.8KW)
DB-4
4TH
F
UNIT-A
Load=7KW
Diversity
Factor-40%
(Load=2.8KW)
DB-5
5TH
F
UNIT-A
Load=7KW
Diversity
Factor-40%
(Load=2.8KW)
DB-6
6TH
F
UNIT-A
Load=7KW
Diversity
Factor-40%
(Load=2.8KW)
DB-7
7TH
F
UNIT-A
Load=7KW
Diversity
Factor-40%
(Load=2.8KW)
DB-8
8TH
F
UNIT-A
Load=7KW
Diversity
Factor-40%
(Load=2.8KW)
DB-1
1ST
F
UNIT-B
Load=7KW
Diversity
Factor-40%
(Load=2.8KW)
DB-1
1ST
F
UNIT-C
Load=7KW
Diversity
Factor-40%
(Load=2.8KW)
DB-1
1ST
F
UNIT-D
Load=7KW
Diversity
Factor-40%
(Load=2.8KW)
DB-2
2ND
F
UNIT-B
Load=7KW
Diversity
Factor-40%
(Load=2.8KW)
DB-2
2ND
F
UNIT-C
Load=7KW
Diversity
Factor-40%
(Load=2.8KW)
DB-2
2ND
F
UNIT-D
Load=7KW
Diversity
Factor-40%
(Load=2.8KW)
DB-3
3RD
F
UNIT-B
Load=7KW
Diversity
Factor-40%
(Load=2.8KW)
DB-3
3RD
F
UNIT-C
Load=7KW
Diversity
Factor-40%
(Load=2.8KW)
DB-3
3RD
F
UNIT-D
Load=7KW
Diversity
Factor-40%
(Load=2.8KW)
DB-4
4TH
F
UNIT-B
Load=7KW
Diversity
Factor-40%
(Load=2.8KW)
DB-4
4TH
F
UNIT-C
Load=7KW
Diversity
Factor-40%
(Load=2.8KW)
DB-4
4TH
F
UNIT-D
Load=7KW
Diversity
Factor-40%
(Load=2.8KW)
DB-5
5TH
F
UNIT-B
Load=7KW
Diversity
Factor-40%
(Load=2.8KW)
DB-5
5TH
F
UNIT-C
Load=7KW
Diversity
Factor-40%
(Load=2.8KW)
DB-5
5TH
F
UNIT-D
Load=7KW
Diversity
Factor-40%
(Load=2.8KW)
DB-6
6TH
F
UNIT-B
Load=7KW
Diversity
Factor-40%
(Load=2.8KW)
DB-6
6TH
F
UNIT-C
Load=7KW
Diversity
Factor-40%
(Load=2.8KW)
DB-6
6TH
F
UNIT-D
Load=7KW
Diversity
Factor-40%
(Load=2.8KW)
DB-7
7TH
F
UNIT-B
Load=7KW
Diversity
Factor-40%
(Load=2.8KW)
DB-7
7TH
F
UNIT-C
Load=7KW
Diversity
Factor-40%
(Load=2.8KW)
DB-7
7TH
F
UNIT-D
Load=7KW
Diversity
Factor-40%
(Load=2.8KW)
CKT-
34
CKT-
35
CKT-
36
CKT-
37
CKT-
38
CKT-
39
CKT-
40
CKT-
41
CKT-
42
CKT-
43
CKT-
44
CKT-
45
CKT-
46
CKT-
47
CKT-
48
40A
DP
MCB
1CX2X10
Sqmm
(SP+N)
BYA
ECC
1CX1X6
Sqmm
BYA
40A
DP
MCB
1CX2X10
Sqmm
(SP+N)
BYA
ECC
1CX1X6
Sqmm
BYA
40A
DP
MCB
1CX2X10
Sqmm
(SP+N)
BYA
ECC
1CX1X6
Sqmm
BYA
40A
DP
MCB
1CX2X10
Sqmm
(SP+N)
BYA
ECC
1CX1X6
Sqmm
BYA
40A
DP
MCB
1CX2X10
Sqmm
(SP+N)
BYA
ECC
1CX1X6
Sqmm
BYA
40A
DP
MCB
1CX2X10
Sqmm
(SP+N)
BYA
ECC
1CX1X6
Sqmm
BYA
40A
DP
MCB
1CX2X10
Sqmm
(SP+N)
BYA
ECC
1CX1X6
Sqmm
BYA
40A
DP
MCB
1CX2X10
Sqmm
(SP+N)
BYA
ECC
1CX1X6
Sqmm
BYA
40A
DP
MCB
1CX2X10
Sqmm
(SP+N)
BYA
ECC
1CX1X6
Sqmm
BYA
40A
DP
MCB
1CX2X10
Sqmm
(SP+N)
BYA
ECC
1CX1X6
Sqmm
BYA
40A
DP
MCB
1CX2X10
Sqmm
(SP+N)
BYA
ECC
1CX1X6
Sqmm
BYA
40A
DP
MCB
1CX2X10
Sqmm
(SP+N)
BYA
ECC
1CX1X6
Sqmm
BYA
40A
DP
MCB
1CX2X10
Sqmm
(SP+N)
BYA
ECC
1CX1X6
Sqmm
BYA
40A
DP
MCB
1CX2X10
Sqmm
(SP+N)
BYA
ECC
1CX1X6
Sqmm
BYA
40A
DP
MCB
1CX2X10
Sqmm
(SP+N)
BYA
ECC
1CX1X6
Sqmm
BYA
40A
DP
MCB
1CX2X10
Sqmm
(SP+N)
BYA
ECC
1CX1X6
Sqmm
BYA
40A
DP
MCB
1CX2X10
Sqmm
(SP+N)
BYA
ECC
1CX1X6
Sqmm
BYA
40A
DP
MCB
1CX2X10
Sqmm
(SP+N)
BYA
ECC
1CX1X6
Sqmm
BYA
40A
DP
MCB
1CX2X10
Sqmm
(SP+N)
BYA
ECC
1CX1X6
Sqmm
BYA
40A
DP
MCB
1CX2X10
Sqmm
(SP+N)
BYA
ECC
1CX1X6
Sqmm
BYA
CKT-
49
CKT-
51
CKT-
52
CKT-
53
40A
DP
MCB
1CX2X10
Sqmm
(SP+N)
BYA
ECC
1CX1X6
Sqmm
BYA
CKT-
54
40A
DP
MCB
1CX2X10
Sqmm
(SP+N)
BYA
ECC
1CX1X6
Sqmm
BYA
CKT-
55
DB-8
8TH
F
UNIT-B
Load=7KW
Diversity
Factor-40%
(Load=2.8KW)
DB-8
8TH
F
UNIT-C
Load=7KW
Diversity
Factor-40%
(Load=2.8KW)
DB-8
8TH
F
UNIT-D
Load=7KW
Diversity
Factor-40%
(Load=2.8KW)
CKT-
50
DB-9
9TH
F
UNIT-A
Load=7KW
Diversity
Factor-40%
(Load=2.8KW)
DB-9
9TH
F
UNIT-B
Load=7KW
Diversity
Factor-40%
(Load=2.8KW)
DB-9
9TH
F
UNIT-C
Load=7KW
Diversity
Factor-40%
(Load=2.8KW)
DB-9
9TH
F
UNIT-D
Load=7KW
Diversity
Factor-40%
(Load=2.8KW)
DB-10
10TH
F
UNIT-A
Load=7KW
Diversity
Factor-40%
(Load=2.8KW)
DB-10
10TH
F
UNIT-B
Load=7KW
Diversity
Factor-40%
(Load=2.8KW)
DB-10
10TH
F
UNIT-C
Load=7KW
Diversity
Factor-40%
(Load=2.8KW)
DB-10
10TH
F
UNIT-D
Load=7KW
Diversity
Factor-40%
(Load=2.8KW)
DB-11
11TH
F
UNIT-A
Load=7KW
Diversity
Factor-40%
(Load=2.8KW)
DB-11
11TH
F
UNIT-B
Load=7KW
Diversity
Factor-40%
(Load=2.8KW)
DB-11
11TH
F
UNIT-C
Load=7KW
Diversity
Factor-40%
(Load=2.8KW)
DB-11
11TH
F
UNIT-D
Load=7KW
Diversity
Factor-40%
(Load=2.8KW)
DB-12
12TH
F
UNIT-A
Load=7KW
Diversity
Factor-40%
(Load=2.8KW)
DB-12
12TH
F
UNIT-B
Load=7KW
Diversity
Factor-40%
(Load=2.8KW)
DB-12
12TH
F
UNIT-C
Load=7KW
Diversity
Factor-40%
(Load=2.8KW)
DB-12
12TH
F
UNIT-D
Load=7KW
Diversity
Factor-40%
(Load=2.8KW)
DB-13
13TH
F
UNIT-A
Load=7KW
Diversity
Factor-40%
(Load=2.8KW)
40A
DP
MCB
1CX2X10
Sqmm
(SP+N)
BYA
ECC
1CX1X6
Sqmm
BYA
CKT-
56
40A
DP
MCB
CKT-
57
40A
DP
MCB
CKT-
58
DB-13
13TH
F
UNIT-B
Load=7KW
Diversity
Factor-40%
(Load=2.8KW)
DB-13
13TH
F
UNIT-C
Load=7KW
Diversity
Factor-40%
(Load=2.8KW)
DB-13
13TH
F
UNIT-D
Load=7KW
Diversity
Factor-40%
(Load=2.8KW)
SPARE
SPARE
R
B
Y
B
R
B
Y
R
B
Y
R
B
Y
R
B
Y
R
B
Y
R
B
Y
R
B
Y
R
B
Y
R
B
Y
R
B
Y
R
B
Y
R
B
Y
R
B
Y
R
B
Y
R
B
Y
R
B
Y
R
B
Y
R
Y
1CX4XX70
Sqmm
(TP+N)
NYY
ECC-
1CX1X35
Sqmm
BYA
200A
TP
MCCB
R
B
YFire
Pump
DB
Load=80kw
1CX4XX70
Sqmm
(TP+N)
NYY
ECC-
1CX1X35
Sqmm
BYA
40A
TP
MCCB
Lift
DB
Load=15kw
1CX4XX70
Sqmm
(TP+N)
NYY
ECC-
1CX1X35
Sqmm
BYA
40A
TP
MCCB
Lift
DB
Load=15kw
1CX4XX70
Sqmm
(TP+N)
NYY
ECC-
1CX1X35
Sqmm
BYA
40A
TP
MCCB
Lift
DB
Load=15kw
R
B
Y
R
B
Y
R
B
Y
CKT-59
1CX4XX70
Sqmm
(TP+N)
NYY
ECC-
1CX1X35
Sqmm
BYA
40A
TP
MCCB
Lift
DB
Load=15kw
R
B
Y
LBS
12.7mm Dia Cu Conductor
EARTH PIT-2
12.7mm Dia Cu Conductor
EARTH PIT-1
PROJECT NAME & ADDRESS:
OWNER'S NAME / REPRESENTATIVE
PREPARED BY
ENGINEER
FIRE PROFESSIONAL
APPROVED BY
DEPARTMENT OF FIRE SERVICE
& CIVIL DEFENSE.
Head Office: 38-46, Road:
KaziAlauddin Road, Siddique Bazar, Dhaka.
SCALE
PAGE SIZE:
1:100
21-12-2021
A-3
DATE
CONSULTANT:
DESIGNER
ARCHITECT
PROPOSED 16 - STORIED RESIDENTIAL BUILDING
AT PLOT NO-03, ROAD NO - 201, SECTOR NO-02,
UNITED CITY, MADANI AVENUE, SATARKUL, DHAKA.
CS DAG - 391, RS DAG - 233 & 234
MOUZA - SATARKUL, PS - BADDA, DHAKA.
AHMED YOUSUF HOSSAIN
S/O - Mohammad Abdul Bari
MOTHERS NAME -Asiya Bari
House # 7, Flat # C/2, Road-04. Gulshan # 1,Dhaka-1212.
MART ENGINEERING & CONSULTANCY
Address: House -10,Road-03,(1st FL), Middle Badda, Gulshan
Badda Link ,Road, Dhaka-1212.
Mobile : +88017 - 17432054
PAGE NO : 17

Mais conteúdo relacionado

Semelhante a Fire safery plan of Ysuf ahmead by Bangladesh

Document for Handing over the building
Document for Handing over the buildingDocument for Handing over the building
Document for Handing over the buildingVj NiroSh
 
Building Technology 2
Building Technology 2Building Technology 2
Building Technology 2nadiacbass
 
Brisbane ferries project drawings
Brisbane ferries project drawingsBrisbane ferries project drawings
Brisbane ferries project drawingsGirish Ravikumar
 
Royal Museum Alor Setar
Royal Museum Alor SetarRoyal Museum Alor Setar
Royal Museum Alor Setarshacjhow
 
Measured drawings
Measured drawingsMeasured drawings
Measured drawingsjiuaN59
 
02 QUALITY CONTROL TEST REPORTS FORMATS
02 QUALITY CONTROL TEST REPORTS FORMATS02 QUALITY CONTROL TEST REPORTS FORMATS
02 QUALITY CONTROL TEST REPORTS FORMATSMary Calkins
 
Red Reedbuck Bush Lodge
Red Reedbuck Bush LodgeRed Reedbuck Bush Lodge
Red Reedbuck Bush LodgeGrant Hepburn
 
Last Eden Eco Bush Lodge
Last Eden Eco Bush LodgeLast Eden Eco Bush Lodge
Last Eden Eco Bush LodgeGrant Hepburn
 
AR-18.pdf
AR-18.pdfAR-18.pdf
AR-18.pdfNicksy1
 
03 drawings stormwater drainage
03 drawings   stormwater drainage03 drawings   stormwater drainage
03 drawings stormwater drainageSylvesterRakgate1
 
15-Great Northern Hotel,Newcastle
15-Great Northern Hotel,Newcastle15-Great Northern Hotel,Newcastle
15-Great Northern Hotel,NewcastleMike Darwich
 
Farmers Agoura Hills CEO Office
Farmers Agoura Hills CEO OfficeFarmers Agoura Hills CEO Office
Farmers Agoura Hills CEO OfficeRichard Clark
 
Prestige Lavender Fields Bangalore - PDF.pdf
Prestige Lavender Fields Bangalore - PDF.pdfPrestige Lavender Fields Bangalore - PDF.pdf
Prestige Lavender Fields Bangalore - PDF.pdfmonikasharma630
 
Final Docket For LP Store Chennai,
Final Docket For LP Store Chennai,Final Docket For LP Store Chennai,
Final Docket For LP Store Chennai,NIZAM ISMAIL
 
Architectural and drafting sample, residential house design, NSW
Architectural and drafting sample, residential house design, NSWArchitectural and drafting sample, residential house design, NSW
Architectural and drafting sample, residential house design, NSWAlexeyRyabchenko
 

Semelhante a Fire safery plan of Ysuf ahmead by Bangladesh (20)

Document for Handing over the building
Document for Handing over the buildingDocument for Handing over the building
Document for Handing over the building
 
Building Technology 2
Building Technology 2Building Technology 2
Building Technology 2
 
ProcContSite
ProcContSiteProcContSite
ProcContSite
 
LA FLORESTA
LA FLORESTALA FLORESTA
LA FLORESTA
 
Brisbane ferries project drawings
Brisbane ferries project drawingsBrisbane ferries project drawings
Brisbane ferries project drawings
 
20150330_R4D_Permit Set
20150330_R4D_Permit Set20150330_R4D_Permit Set
20150330_R4D_Permit Set
 
Royal Museum Alor Setar
Royal Museum Alor SetarRoyal Museum Alor Setar
Royal Museum Alor Setar
 
Measured drawings
Measured drawingsMeasured drawings
Measured drawings
 
Masters s
Masters sMasters s
Masters s
 
02 QUALITY CONTROL TEST REPORTS FORMATS
02 QUALITY CONTROL TEST REPORTS FORMATS02 QUALITY CONTROL TEST REPORTS FORMATS
02 QUALITY CONTROL TEST REPORTS FORMATS
 
Red Reedbuck Bush Lodge
Red Reedbuck Bush LodgeRed Reedbuck Bush Lodge
Red Reedbuck Bush Lodge
 
Last Eden Eco Bush Lodge
Last Eden Eco Bush LodgeLast Eden Eco Bush Lodge
Last Eden Eco Bush Lodge
 
AR-18.pdf
AR-18.pdfAR-18.pdf
AR-18.pdf
 
Dbr
DbrDbr
Dbr
 
03 drawings stormwater drainage
03 drawings   stormwater drainage03 drawings   stormwater drainage
03 drawings stormwater drainage
 
15-Great Northern Hotel,Newcastle
15-Great Northern Hotel,Newcastle15-Great Northern Hotel,Newcastle
15-Great Northern Hotel,Newcastle
 
Farmers Agoura Hills CEO Office
Farmers Agoura Hills CEO OfficeFarmers Agoura Hills CEO Office
Farmers Agoura Hills CEO Office
 
Prestige Lavender Fields Bangalore - PDF.pdf
Prestige Lavender Fields Bangalore - PDF.pdfPrestige Lavender Fields Bangalore - PDF.pdf
Prestige Lavender Fields Bangalore - PDF.pdf
 
Final Docket For LP Store Chennai,
Final Docket For LP Store Chennai,Final Docket For LP Store Chennai,
Final Docket For LP Store Chennai,
 
Architectural and drafting sample, residential house design, NSW
Architectural and drafting sample, residential house design, NSWArchitectural and drafting sample, residential house design, NSW
Architectural and drafting sample, residential house design, NSW
 

Último

The history of music videos a level presentation
The history of music videos a level presentationThe history of music videos a level presentation
The history of music videos a level presentationamedia6
 
VIP Kolkata Call Girl Gariahat 👉 8250192130 Available With Room
VIP Kolkata Call Girl Gariahat 👉 8250192130  Available With RoomVIP Kolkata Call Girl Gariahat 👉 8250192130  Available With Room
VIP Kolkata Call Girl Gariahat 👉 8250192130 Available With Roomdivyansh0kumar0
 
PORTAFOLIO 2024_ ANASTASIYA KUDINOVA
PORTAFOLIO   2024_  ANASTASIYA  KUDINOVAPORTAFOLIO   2024_  ANASTASIYA  KUDINOVA
PORTAFOLIO 2024_ ANASTASIYA KUDINOVAAnastasiya Kudinova
 
VIP Call Girls Service Bhagyanagar Hyderabad Call +91-8250192130
VIP Call Girls Service Bhagyanagar Hyderabad Call +91-8250192130VIP Call Girls Service Bhagyanagar Hyderabad Call +91-8250192130
VIP Call Girls Service Bhagyanagar Hyderabad Call +91-8250192130Suhani Kapoor
 
Dubai Call Girls Pro Domain O525547819 Call Girls Dubai Doux
Dubai Call Girls Pro Domain O525547819 Call Girls Dubai DouxDubai Call Girls Pro Domain O525547819 Call Girls Dubai Doux
Dubai Call Girls Pro Domain O525547819 Call Girls Dubai Douxkojalkojal131
 
WAEC Carpentry and Joinery Past Questions
WAEC Carpentry and Joinery Past QuestionsWAEC Carpentry and Joinery Past Questions
WAEC Carpentry and Joinery Past QuestionsCharles Obaleagbon
 
Kieran Salaria Graphic Design PDF Portfolio
Kieran Salaria Graphic Design PDF PortfolioKieran Salaria Graphic Design PDF Portfolio
Kieran Salaria Graphic Design PDF Portfolioktksalaria
 
Cosumer Willingness to Pay for Sustainable Bricks
Cosumer Willingness to Pay for Sustainable BricksCosumer Willingness to Pay for Sustainable Bricks
Cosumer Willingness to Pay for Sustainable Bricksabhishekparmar618
 
SD_The MATATAG Curriculum Training Design.pptx
SD_The MATATAG Curriculum Training Design.pptxSD_The MATATAG Curriculum Training Design.pptx
SD_The MATATAG Curriculum Training Design.pptxjanettecruzeiro1
 
Chapter 19_DDA_TOD Policy_First Draft 2012.pdf
Chapter 19_DDA_TOD Policy_First Draft 2012.pdfChapter 19_DDA_TOD Policy_First Draft 2012.pdf
Chapter 19_DDA_TOD Policy_First Draft 2012.pdfParomita Roy
 
Fashion trends before and after covid.pptx
Fashion trends before and after covid.pptxFashion trends before and after covid.pptx
Fashion trends before and after covid.pptxVanshNarang19
 
Call Us ✡️97111⇛47426⇛Call In girls Vasant Vihar༒(Delhi)
Call Us ✡️97111⇛47426⇛Call In girls Vasant Vihar༒(Delhi)Call Us ✡️97111⇛47426⇛Call In girls Vasant Vihar༒(Delhi)
Call Us ✡️97111⇛47426⇛Call In girls Vasant Vihar༒(Delhi)jennyeacort
 
Kala jadu for love marriage | Real amil baba | Famous amil baba | kala jadu n...
Kala jadu for love marriage | Real amil baba | Famous amil baba | kala jadu n...Kala jadu for love marriage | Real amil baba | Famous amil baba | kala jadu n...
Kala jadu for love marriage | Real amil baba | Famous amil baba | kala jadu n...babafaisel
 
Raj Nagar Extension Call Girls 9711199012 WhatsApp No, Delhi Escorts in Raj N...
Raj Nagar Extension Call Girls 9711199012 WhatsApp No, Delhi Escorts in Raj N...Raj Nagar Extension Call Girls 9711199012 WhatsApp No, Delhi Escorts in Raj N...
Raj Nagar Extension Call Girls 9711199012 WhatsApp No, Delhi Escorts in Raj N...ankitnayak356677
 
VVIP Pune Call Girls Hadapsar (7001035870) Pune Escorts Nearby with Complete ...
VVIP Pune Call Girls Hadapsar (7001035870) Pune Escorts Nearby with Complete ...VVIP Pune Call Girls Hadapsar (7001035870) Pune Escorts Nearby with Complete ...
VVIP Pune Call Girls Hadapsar (7001035870) Pune Escorts Nearby with Complete ...Call Girls in Nagpur High Profile
 
NATA 2024 SYLLABUS, full syllabus explained in detail
NATA 2024 SYLLABUS, full syllabus explained in detailNATA 2024 SYLLABUS, full syllabus explained in detail
NATA 2024 SYLLABUS, full syllabus explained in detailDesigntroIntroducing
 
Kurla Call Girls Pooja Nehwal📞 9892124323 ✅ Vashi Call Service Available Nea...
Kurla Call Girls Pooja Nehwal📞 9892124323 ✅  Vashi Call Service Available Nea...Kurla Call Girls Pooja Nehwal📞 9892124323 ✅  Vashi Call Service Available Nea...
Kurla Call Girls Pooja Nehwal📞 9892124323 ✅ Vashi Call Service Available Nea...Pooja Nehwal
 
CALL ON ➥8923113531 🔝Call Girls Aminabad Lucknow best Night Fun service
CALL ON ➥8923113531 🔝Call Girls Aminabad Lucknow best Night Fun serviceCALL ON ➥8923113531 🔝Call Girls Aminabad Lucknow best Night Fun service
CALL ON ➥8923113531 🔝Call Girls Aminabad Lucknow best Night Fun serviceanilsa9823
 
Call Girls In Safdarjung Enclave 24/7✡️9711147426✡️ Escorts Service
Call Girls In Safdarjung Enclave 24/7✡️9711147426✡️ Escorts ServiceCall Girls In Safdarjung Enclave 24/7✡️9711147426✡️ Escorts Service
Call Girls In Safdarjung Enclave 24/7✡️9711147426✡️ Escorts Servicejennyeacort
 

Último (20)

The history of music videos a level presentation
The history of music videos a level presentationThe history of music videos a level presentation
The history of music videos a level presentation
 
VIP Kolkata Call Girl Gariahat 👉 8250192130 Available With Room
VIP Kolkata Call Girl Gariahat 👉 8250192130  Available With RoomVIP Kolkata Call Girl Gariahat 👉 8250192130  Available With Room
VIP Kolkata Call Girl Gariahat 👉 8250192130 Available With Room
 
PORTAFOLIO 2024_ ANASTASIYA KUDINOVA
PORTAFOLIO   2024_  ANASTASIYA  KUDINOVAPORTAFOLIO   2024_  ANASTASIYA  KUDINOVA
PORTAFOLIO 2024_ ANASTASIYA KUDINOVA
 
VIP Call Girls Service Bhagyanagar Hyderabad Call +91-8250192130
VIP Call Girls Service Bhagyanagar Hyderabad Call +91-8250192130VIP Call Girls Service Bhagyanagar Hyderabad Call +91-8250192130
VIP Call Girls Service Bhagyanagar Hyderabad Call +91-8250192130
 
Call Girls Service Mukherjee Nagar @9999965857 Delhi 🫦 No Advance VVIP 🍎 SER...
Call Girls Service Mukherjee Nagar @9999965857 Delhi 🫦 No Advance  VVIP 🍎 SER...Call Girls Service Mukherjee Nagar @9999965857 Delhi 🫦 No Advance  VVIP 🍎 SER...
Call Girls Service Mukherjee Nagar @9999965857 Delhi 🫦 No Advance VVIP 🍎 SER...
 
Dubai Call Girls Pro Domain O525547819 Call Girls Dubai Doux
Dubai Call Girls Pro Domain O525547819 Call Girls Dubai DouxDubai Call Girls Pro Domain O525547819 Call Girls Dubai Doux
Dubai Call Girls Pro Domain O525547819 Call Girls Dubai Doux
 
WAEC Carpentry and Joinery Past Questions
WAEC Carpentry and Joinery Past QuestionsWAEC Carpentry and Joinery Past Questions
WAEC Carpentry and Joinery Past Questions
 
Kieran Salaria Graphic Design PDF Portfolio
Kieran Salaria Graphic Design PDF PortfolioKieran Salaria Graphic Design PDF Portfolio
Kieran Salaria Graphic Design PDF Portfolio
 
Cosumer Willingness to Pay for Sustainable Bricks
Cosumer Willingness to Pay for Sustainable BricksCosumer Willingness to Pay for Sustainable Bricks
Cosumer Willingness to Pay for Sustainable Bricks
 
SD_The MATATAG Curriculum Training Design.pptx
SD_The MATATAG Curriculum Training Design.pptxSD_The MATATAG Curriculum Training Design.pptx
SD_The MATATAG Curriculum Training Design.pptx
 
Chapter 19_DDA_TOD Policy_First Draft 2012.pdf
Chapter 19_DDA_TOD Policy_First Draft 2012.pdfChapter 19_DDA_TOD Policy_First Draft 2012.pdf
Chapter 19_DDA_TOD Policy_First Draft 2012.pdf
 
Fashion trends before and after covid.pptx
Fashion trends before and after covid.pptxFashion trends before and after covid.pptx
Fashion trends before and after covid.pptx
 
Call Us ✡️97111⇛47426⇛Call In girls Vasant Vihar༒(Delhi)
Call Us ✡️97111⇛47426⇛Call In girls Vasant Vihar༒(Delhi)Call Us ✡️97111⇛47426⇛Call In girls Vasant Vihar༒(Delhi)
Call Us ✡️97111⇛47426⇛Call In girls Vasant Vihar༒(Delhi)
 
Kala jadu for love marriage | Real amil baba | Famous amil baba | kala jadu n...
Kala jadu for love marriage | Real amil baba | Famous amil baba | kala jadu n...Kala jadu for love marriage | Real amil baba | Famous amil baba | kala jadu n...
Kala jadu for love marriage | Real amil baba | Famous amil baba | kala jadu n...
 
Raj Nagar Extension Call Girls 9711199012 WhatsApp No, Delhi Escorts in Raj N...
Raj Nagar Extension Call Girls 9711199012 WhatsApp No, Delhi Escorts in Raj N...Raj Nagar Extension Call Girls 9711199012 WhatsApp No, Delhi Escorts in Raj N...
Raj Nagar Extension Call Girls 9711199012 WhatsApp No, Delhi Escorts in Raj N...
 
VVIP Pune Call Girls Hadapsar (7001035870) Pune Escorts Nearby with Complete ...
VVIP Pune Call Girls Hadapsar (7001035870) Pune Escorts Nearby with Complete ...VVIP Pune Call Girls Hadapsar (7001035870) Pune Escorts Nearby with Complete ...
VVIP Pune Call Girls Hadapsar (7001035870) Pune Escorts Nearby with Complete ...
 
NATA 2024 SYLLABUS, full syllabus explained in detail
NATA 2024 SYLLABUS, full syllabus explained in detailNATA 2024 SYLLABUS, full syllabus explained in detail
NATA 2024 SYLLABUS, full syllabus explained in detail
 
Kurla Call Girls Pooja Nehwal📞 9892124323 ✅ Vashi Call Service Available Nea...
Kurla Call Girls Pooja Nehwal📞 9892124323 ✅  Vashi Call Service Available Nea...Kurla Call Girls Pooja Nehwal📞 9892124323 ✅  Vashi Call Service Available Nea...
Kurla Call Girls Pooja Nehwal📞 9892124323 ✅ Vashi Call Service Available Nea...
 
CALL ON ➥8923113531 🔝Call Girls Aminabad Lucknow best Night Fun service
CALL ON ➥8923113531 🔝Call Girls Aminabad Lucknow best Night Fun serviceCALL ON ➥8923113531 🔝Call Girls Aminabad Lucknow best Night Fun service
CALL ON ➥8923113531 🔝Call Girls Aminabad Lucknow best Night Fun service
 
Call Girls In Safdarjung Enclave 24/7✡️9711147426✡️ Escorts Service
Call Girls In Safdarjung Enclave 24/7✡️9711147426✡️ Escorts ServiceCall Girls In Safdarjung Enclave 24/7✡️9711147426✡️ Escorts Service
Call Girls In Safdarjung Enclave 24/7✡️9711147426✡️ Escorts Service
 

Fire safery plan of Ysuf ahmead by Bangladesh

  • 1. Ref No:MEC:Dhaka:April:2022:18 PROPOSED FIRE SAFETY PLAN DRAWING PROJECT NAME AND ADDRESS DR. MD. ABDUL WAKIL OWNER'S NAME OCCUPANCY CLASSIFICATION BUILDING TYPE PREPARED BY A2 R.C.C BUILDING MART ENGINEERING & CONSULTANCY HOTLINE:-01717-432054, 01670-212478 ENGR. M.A. RASHID TIPU,CFPS Certified Fire Protection Specialist Ba-08, South Badda, Gulshan, (Behind of shooting club) Dhaka-1212, Bangladesh. Mobile:-01717-432054, 01670-212478 APPROVED BY DEPARTMENT OF FIRE SERVICE & CIVIL DEFENSE 38-46, ROAD-KAZI-ALAUDDIN ROAD, SIDDIQUE BAZAR, DHAKA 1000 FAISAL MAHBUB IAB Membership & Rajuk Registration No-M-015 Cell: 01980001277 ARCHITECT : AHMED YOUSUF HOSSAIN HOUSE # 7, FLAT # C/2, ROAD-04. GULSHAN # 1, DHAKA-1212 OWNER'S NAME : WE KILL FIRE BEFORE IT KILLS YOU CONSULTANT: PROPOSED 16 - STORIED RESIDENTIAL BUILDING AT PLOT NO-03, ROAD NO - 201, SECTOR NO-02, UNITED CITY, MADANI AVENUE, SATARKUL, DHAKA. CS DAG - 391, RS DAG - 233 & 234 MOUZA - SATARKUL, PS - BADDA, DHAKA.
  • 2. LAYOUT DRAWING OF GROUND FLOOR 05 06 07 09 INDEX & LEGEND 00 TOP SHEET 01 02 03 04 08 LAYOUT DRAWING OF 1ST FLOOR MASTER PLAN MASTER PLAN 10 POSITIVE SUCTION FIRE PUMP SCHEMATIC DIAGRAM AND INSTALLATION DETAILING FIRE ALARM RISER DIAGRAM ELEVATION & SECTION VIEW 11 BUILDING AREA : RESIDENTIAL & REFUGE AREA LAYOUT DRAWING OF SUBSTATION INSTRUCTIONS: SUB-STATION ROOM ROOF FLOOR : PROPOSED LIGHTING PROTECTION SYSTEM (LPS). 13 PAGE NO. DRAWING TITLE DESCRIPTION INDEX 12 GOOGLE MAP FIRE PUMP ROOM, WATER RESERVOIR,PARKING AREA 14 FIRE CONTROL PANEL & 150 KVA SUBSTATION ROOM, 100 KVA GENERATOR & PARKING AREA PROPOSED SINGLE LINE DIAGRAM (SLD) 15 COMMUNITY HALL R. S MOUZA MAP LAYOUT DRAWING OF 2ND TO 14TH FLOOR LAYOUT DRAWING OF 8TH FLOOR LAYOUT DRAWING OF 15TH FLOOR & ROOF FLOOR RESIDENTIAL AREA ROOF OF COMMON ROOM 16 PROJECT NAME & ADDRESS: OWNER'S NAME / REPRESENTATIVE PREPARED BY ENGINEER FIRE PROFESSIONAL APPROVED BY DEPARTMENT OF FIRE SERVICE & CIVIL DEFENSE. Head Office: 38-46, Road: KaziAlauddin Road, Siddique Bazar, Dhaka. SCALE PAGE SIZE: 1:100 21-12-2021 A-3 DATE CONSULTANT: DESIGNER ARCHITECT PROPOSED 16 - STORIED RESIDENTIAL BUILDING AT PLOT NO-03, ROAD NO - 201, SECTOR NO-02, UNITED CITY, MADANI AVENUE, SATARKUL, DHAKA. CS DAG - 391, RS DAG - 233 & 234 MOUZA - SATARKUL, PS - BADDA, DHAKA. AHMED YOUSUF HOSSAIN S/O - Mohammad Abdul Bari MOTHERS NAME -Asiya Bari House # 7, Flat # C/2, Road-04. Gulshan # 1,Dhaka-1212. MART ENGINEERING & CONSULTANCY Address: House -10,Road-03,(1st FL), Middle Badda, Gulshan Badda Link ,Road, Dhaka-1212. Mobile : +88017 - 17432054 PAGE NO : 01
  • 3. Total area 01 1st Floor (Community) 122.26 Sl. No. Floor Total (Sqm) 14 15th Floor / Roof Floor 105.90 02 2nd Floor 223.27 03 3rd Floor 04 4th Floor 05 5th Floor 06 6th Floor 07 7th Floor 08 8th Floor 09 9th Floor 10 10th Floor 11 11th Floor 12 12th Floor 13 13th Floor 13 14th Floor 223.27 223.27 223.27 223.27 223.27 223.27 223.27 223.27 223.27 223.27 223.27 223.27 Ground floor 348.77 3479.44 TOTAL FLOOR AREA: PROJECT NAME & ADDRESS: OWNER'S NAME / REPRESENTATIVE PREPARED BY ENGINEER FIRE PROFESSIONAL APPROVED BY DEPARTMENT OF FIRE SERVICE & CIVIL DEFENSE. Head Office: 38-46, Road: KaziAlauddin Road, Siddique Bazar, Dhaka. SCALE PAGE SIZE: 1:100 21-12-2021 A-3 DATE CONSULTANT: DESIGNER ARCHITECT PROPOSED 16 - STORIED RESIDENTIAL BUILDING AT PLOT NO-03, ROAD NO - 201, SECTOR NO-02, UNITED CITY, MADANI AVENUE, SATARKUL, DHAKA. CS DAG - 391, RS DAG - 233 & 234 MOUZA - SATARKUL, PS - BADDA, DHAKA. AHMED YOUSUF HOSSAIN S/O - Mohammad Abdul Bari MOTHERS NAME -Asiya Bari House # 7, Flat # C/2, Road-04. Gulshan # 1,Dhaka-1212. MART ENGINEERING & CONSULTANCY Address: House -10,Road-03,(1st FL), Middle Badda, Gulshan Badda Link ,Road, Dhaka-1212. Mobile : +88017 - 17432054 PAGE NO : 02
  • 4. Google Map PROJECT NAME & ADDRESS: OWNER'S NAME / REPRESENTATIVE PREPARED BY ENGINEER FIRE PROFESSIONAL APPROVED BY DEPARTMENT OF FIRE SERVICE & CIVIL DEFENSE. Head Office: 38-46, Road: KaziAlauddin Road, Siddique Bazar, Dhaka. SCALE PAGE SIZE: 1:100 21-12-2021 A-3 DATE CONSULTANT: DESIGNER ARCHITECT PROPOSED 16 - STORIED RESIDENTIAL BUILDING AT PLOT NO-03, ROAD NO - 201, SECTOR NO-02, UNITED CITY, MADANI AVENUE, SATARKUL, DHAKA. CS DAG - 391, RS DAG - 233 & 234 MOUZA - SATARKUL, PS - BADDA, DHAKA. AHMED YOUSUF HOSSAIN S/O - Mohammad Abdul Bari MOTHERS NAME -Asiya Bari House # 7, Flat # C/2, Road-04. Gulshan # 1,Dhaka-1212. MART ENGINEERING & CONSULTANCY Address: House -10,Road-03,(1st FL), Middle Badda, Gulshan Badda Link ,Road, Dhaka-1212. Mobile : +88017 - 17432054 PAGE NO : 04
  • 5. 1 8 . 2 9 m W I D E R O A D 19.65m 22.11m 2 0 .0 0 m 25.61m FIRE STAIR 5.08mx2.00m FIRE LIFT 1.96mx2.44m GUARD POST 2.38mx1.40m E N T R Y E X IT GREEN GREEN GREEN GREEN GREEN GREEN 3.16m 3.05m SW SEPTIC TANK TO SURFACE DRAIN LT Panel PROPOSED UNDER GROUND FIRE WATER RESERVOIR 50,000 US GALLON Switchgear room 10'-3X7'-3" 150KVA Transformer Room 100KVA Generator Room FHC Standpipe Riser & Drain Pipe Fire Hose Connection Ø65mm Landing valve FDC Ø150mm Pillar Hydrant 2 WAY(65MM) FIRE DEPARTMENT CONNECTION Ø150mm Underground Pipe Fire Control Room PROPOSED 16 - STORIED RESIDENTIAL BUILDING STAIR 2.87mx4.27m PROPOSED FIRE PUMP ROOM N MASTER PLAN SCALE :- 1 : 200 PROJECT NAME & ADDRESS: OWNER'S NAME / REPRESENTATIVE PREPARED BY ENGINEER FIRE PROFESSIONAL APPROVED BY DEPARTMENT OF FIRE SERVICE & CIVIL DEFENSE. Head Office: 38-46, Road: KaziAlauddin Road, Siddique Bazar, Dhaka. SCALE PAGE SIZE: 1:100 21-12-2021 A-3 DATE CONSULTANT: DESIGNER ARCHITECT PROPOSED 16 - STORIED RESIDENTIAL BUILDING AT PLOT NO-03, ROAD NO - 201, SECTOR NO-02, UNITED CITY, MADANI AVENUE, SATARKUL, DHAKA. CS DAG - 391, RS DAG - 233 & 234 MOUZA - SATARKUL, PS - BADDA, DHAKA. AHMED YOUSUF HOSSAIN S/O - Mohammad Abdul Bari MOTHERS NAME -Asiya Bari House # 7, Flat # C/2, Road-04. Gulshan # 1,Dhaka-1212. MART ENGINEERING & CONSULTANCY Address: House -10,Road-03,(1st FL), Middle Badda, Gulshan Badda Link ,Road, Dhaka-1212. Mobile : +88017 - 17432054 PAGE NO : 05
  • 6. 226 235 234 236 887 227 129 233 902 228 232 128 888 130 N O R. S MOUZA MAP SCALE : 16" = 1 MILE PROPOSED PLOT PROJECT NAME & ADDRESS: OWNER'S NAME / REPRESENTATIVE PREPARED BY ENGINEER FIRE PROFESSIONAL APPROVED BY DEPARTMENT OF FIRE SERVICE & CIVIL DEFENSE. Head Office: 38-46, Road: KaziAlauddin Road, Siddique Bazar, Dhaka. SCALE PAGE SIZE: 1:100 21-12-2021 A-3 DATE CONSULTANT: DESIGNER ARCHITECT PROPOSED 16 - STORIED RESIDENTIAL BUILDING AT PLOT NO-03, ROAD NO - 201, SECTOR NO-02, UNITED CITY, MADANI AVENUE, SATARKUL, DHAKA. CS DAG - 391, RS DAG - 233 & 234 MOUZA - SATARKUL, PS - BADDA, DHAKA. AHMED YOUSUF HOSSAIN S/O - Mohammad Abdul Bari MOTHERS NAME -Asiya Bari House # 7, Flat # C/2, Road-04. Gulshan # 1,Dhaka-1212. MART ENGINEERING & CONSULTANCY Address: House -10,Road-03,(1st FL), Middle Badda, Gulshan Badda Link ,Road, Dhaka-1212. Mobile : +88017 - 17432054 PAGE NO : 03
  • 7. 1 8 . 2 9 m W I D E R O A D 19.65m 22.11m 2 0 .0 0 m 25.61m FIRE STAIR 5.08mx2.00m FIRE LIFT 1.96mx2.44m LIFT LOBBY 2.21mx1.57m STAIR 2.87mx4.27m LIFT 1.96mx1.52m Level + 0.76m GUARD POST 2.38mx1.40m E N T R Y E X IT UP GREEN GREEN GREEN GREEN GREEN GREEN TOILET 1.27mx2.29m DRIVER'S SITTING 1.40mx3.02m D R I V E W A Y 3.16m CAR DROP OFF AREA 3.05m UP SW SEPTIC TANK TO SURFACE DRAIN SYMBOL SYMBOL NAME Q.T 03 Smoke Detector 07 Fire Alarm Control Panel 01 Horn With Light 06 Manual call points P 03 SYMBOL SYMBOL NAME Q.T SYMBOL SYMBOL NAME Q.T 02 Fire Hose Connection Class- III 01 Fire Door 2 Rated 06 17 Sprinkler K- 11.2 FIRST AID BOX 04 Extinguisher (ABC & CO2) 07 ADDRESSABLE OUTPUT MODULE ABC CO2 SYMBOL SYMBOL NAME Q.T 02 02 03 03 FM 200 GAS Nozzle 360° 100 LETTER FM 200 GAS CYLINDER A Actuator P Pressure switch FM-200 System Control Panel 02 Heat Detector NOVEC-1230 FACP FACP POSITIVE AIR PRESSURIZED. GROUND FLOOR: 150KVA SUB-STATION, 100KVA GENERATOR, FIRE CONTROL ROOM & FIRE PUMP ROOM Floor Area:2000.04 sft Scale : 1:100 FOAM FACP FM-200 System Control Panel 100 LETTER FM 200 FOAM CYLINDER FM 200 FOAM Nozzle 360° 01 01 01 N LT Panel EXHAUST SILENCER PROPOSED UNDER GROUND FIRE WATER RESERVOIR 50,000 US GALLON UP DN P 500 GPM ELECTRIC PUMP 500 GPM DIESEL ENGINE PUMP 10 GPM JOCKEY PUMP P Safety Lobby Safety Lobby Fire Control Room 1.27mx1.52m FACP P ABC CO2 100 LETTER CYLINDER 100 LETTER CYLINDER Switchgear room 10'-3X7'-3" P A Exit Exit P A NOVEC-1230 FACP ABC CO2 150KVA Transformer Room 9'-6''x9'-10'' Novec-1230 Gas Fire Suppression System ABC CO2 FOAM FACP Exit 100 LETTER FOAM CYLINDER 100KVA Generator Room 7'-7''x15'-0'' Foam Fire Suppression system NOVEC-1230 FACP ABC CO2 ABC CO2 ABC CO2 ABC CO2 ABC CO2 FHC Standpipe Riser & Drain Pipe Fire Hose Connection ABC CO2 POSITIVE AIR PRESSURIZED. Ø65mm Landing valve 4 HOUR FIRE RATED WALL 4 HOUR RATED WALL 4 HOUR FIRE RATED WALL 4 HOUR FIRE RATED WALL Sprinkler Head Ø25mm Ø25mm Ø25mm Ø25mm Ø25mm Ø32mm Ø25mm Ø25mm Ø25mm Ø25mm Ø25mm Ø25mm Ø25mm Ø25mm Ø25mm Ø32mm Ø50mm Ø25mm Ø25mm Ø65mm Ø65mm Ø65mm Ø65mm Ø50mm WF AIM AIM To Nearest Drain Pit Zone Control Valve P A AIM AIM AIM AIM AIM AIM AIM AIM AIM AIM FHC AIM 12 SYMBOL SYMBOL NAME Q.T 00 Sprinkler K- 11.2 PILLAR HYDRANT 01 FIRST AID BOX 00 01 2 way(65mm) Fire Department Connection FDC PROJECT NAME & ADDRESS: OWNER'S NAME / REPRESENTATIVE PREPARED BY ENGINEER FIRE PROFESSIONAL APPROVED BY DEPARTMENT OF FIRE SERVICE & CIVIL DEFENSE. Head Office: 38-46, Road: KaziAlauddin Road, Siddique Bazar, Dhaka. SCALE PAGE SIZE: 1:100 21-12-2021 A-3 DATE CONSULTANT: DESIGNER ARCHITECT PROPOSED 16 - STORIED RESIDENTIAL BUILDING AT PLOT NO-03, ROAD NO - 201, SECTOR NO-02, UNITED CITY, MADANI AVENUE, SATARKUL, DHAKA. CS DAG - 391, RS DAG - 233 & 234 MOUZA - SATARKUL, PS - BADDA, DHAKA. AHMED YOUSUF HOSSAIN S/O - Mohammad Abdul Bari MOTHERS NAME -Asiya Bari House # 7, Flat # C/2, Road-04. Gulshan # 1,Dhaka-1212. MART ENGINEERING & CONSULTANCY Address: House -10,Road-03,(1st FL), Middle Badda, Gulshan Badda Link ,Road, Dhaka-1212. Mobile : +88017 - 17432054 PAGE NO : 06
  • 8. INSTRUCTIONS: ELECTRICAL SUB STATION ROOM PROJECT NAME & ADDRESS: OWNER'S NAME / REPRESENTATIVE PREPARED BY ENGINEER FIRE PROFESSIONAL APPROVED BY DEPARTMENT OF FIRE SERVICE & CIVIL DEFENSE. Head Office: 38-46, Road: KaziAlauddin Road, Siddique Bazar, Dhaka. SCALE PAGE SIZE: 1:100 21-12-2021 A-3 DATE CONSULTANT: DESIGNER ARCHITECT PROPOSED 16 - STORIED RESIDENTIAL BUILDING AT PLOT NO-03, ROAD NO - 201, SECTOR NO-02, UNITED CITY, MADANI AVENUE, SATARKUL, DHAKA. CS DAG - 391, RS DAG - 233 & 234 MOUZA - SATARKUL, PS - BADDA, DHAKA. AHMED YOUSUF HOSSAIN S/O - Mohammad Abdul Bari MOTHERS NAME -Asiya Bari House # 7, Flat # C/2, Road-04. Gulshan # 1,Dhaka-1212. MART ENGINEERING & CONSULTANCY Address: House -10,Road-03,(1st FL), Middle Badda, Gulshan Badda Link ,Road, Dhaka-1212. Mobile : +88017 - 17432054 PAGE NO : 07
  • 9. LT Panel HT Panel SYMBOL SYMBOL NAME Q.T 03 Heat Detector Smoke Detector 03 ABORT SWITCH 03 Horn With Light 03 Manual call points P 00 Actuator SWITCH 03 PRESSURE SWITCH 03 03 FIRST AID BOX Fire Door 2 Rated 03 A P FM 200 GAS NOZZLE 360° 100 LETTER FM 200 GAS CYLINDER FM-200 System Control Panel 01 Extinguisher (ABC & CO2) 5KG 03 4 HOUR RATED WALL NOVEC-1230 FACP 02 02 FOAM NOZZLE 360° FOAM FACP FOAM System Control Panel 100 LETTER FOAM CYLINDER 01 01 01 Floor Area: 320 sft Scale : 1:100 ABC CO2 AS PER DRAWING ABC CO2 ABC CO2 FOAM FACP Exit 100 LETTER CYLINDER 100 LETTER FOAM CYLINDER 100 LETTER CYLINDER 150KVA Transformer Room 9'-6''x9'-10'' Novec-1230 Gas Fire Suppression System Switchgear room 10'-3X7'-3" 100KVA Generator Room 7'-7''x15'-0'' Foam Fire Suppression system P A 150 KVA Sub-Station, 100 KVA Generator NOVEC 1230 FIRE SUPPRESSION SYSTEM Exit Exit P A NOVEC-1230 FACP ABC CO2 N P A NOVEC-1230 FACP 11'-6" 8'-10" 15'-9" 10'-1" 5'-10" 7'-3" 1. Electric backup for fire Lift 2. Electric backup for Stair case Positive Air Pressure. 3. Electric backup Ventilation system with Cross fresh air 4. Electric backup Fire Pump/Jockey pump 5. All signes Including Backup Emergency Exit sing Generator & Emergency power Generator Room 1. Separation Rating 2. Wall: 4 Hour, Door: 2 Hour Fire Rating 3. Suppression: Clean Agent 4. Capacity :100KVA 5. Location : Ground Floor TRANSFORMER & SWITCHGEAR ROOM 1. Separation Rating 2. Wall: 4 Hour, Door: 2 Hour Fire Rating 3. Suppression: Clean Agent 4. Capacity : 150KVA 5. Location : Ground Floor NOTE: SCHEMATIC DRAWING FOR AUTOMATIC CLEAN AGENT DISTRBUTION SYSTEM FOR SUBSTATION ROOM SIZE APPROXIMATELY 220SFT PROJECT NAME & ADDRESS: OWNER'S NAME / REPRESENTATIVE PREPARED BY ENGINEER FIRE PROFESSIONAL APPROVED BY DEPARTMENT OF FIRE SERVICE & CIVIL DEFENSE. Head Office: 38-46, Road: KaziAlauddin Road, Siddique Bazar, Dhaka. SCALE PAGE SIZE: 1:100 21-12-2021 A-3 DATE CONSULTANT: DESIGNER ARCHITECT PROPOSED 16 - STORIED RESIDENTIAL BUILDING AT PLOT NO-03, ROAD NO - 201, SECTOR NO-02, UNITED CITY, MADANI AVENUE, SATARKUL, DHAKA. CS DAG - 391, RS DAG - 233 & 234 MOUZA - SATARKUL, PS - BADDA, DHAKA. AHMED YOUSUF HOSSAIN S/O - Mohammad Abdul Bari MOTHERS NAME -Asiya Bari House # 7, Flat # C/2, Road-04. Gulshan # 1,Dhaka-1212. MART ENGINEERING & CONSULTANCY Address: House -10,Road-03,(1st FL), Middle Badda, Gulshan Badda Link ,Road, Dhaka-1212. Mobile : +88017 - 17432054 PAGE NO : 08
  • 10. LIFT LOBBY 1.68mx1.57m TOILET 2.21mx1.30m COMMUNITY HALL 7.76mx9.73m ROOF OF ELECTRO- MECHANICAL ROOM UP DN FIRE STAIR 5.08mx2.00m STAIR 2.87mx4.27m Safety Lobby Safety Lobby FHC Standpipe Riser & Drain Pipe Fire Hose Connection Ø65mm Landing valve FIRE LIFT 1.96mx2.44m LIFT 1.96mx1.52m ABC CO2 4 HOUR FIRE RATED WALL 4 HOUR FIRE RATED WALL POSITIVE AIR PRESSURIZED. P SYMBOL SYMBOL NAME Q.T 00 Smoke Detector Fire Alarm Control Panel Horn With Light Manual call points P SYMBOL SYMBOL NAME Q.T SYMBOL SYMBOL NAME Q.T Standpipe Riser & Drain Pipe 01 Fire Hose Connection Class- III Fire Door 2 Rated 00 Sprinkler K- 11.2 PILLAR HYDRANT 01 FIRST AID BOX 00 Extinguisher (ABC & CO2) 00 01 2 way(65mm) Fire Department Connection 4 HOUR RATED WALL ABC CO2 Heat Detector FDC FACP POSITIVE AIR PRESSURIZED. 1ST FLOOR: FACP ROOM & RESIDENTIAL AREA Floor Area:122.26Sqm Scale : 1:100 06 01 01 02 01 04 AS PER DRAWING 01 N FHC PROJECT NAME & ADDRESS: OWNER'S NAME / REPRESENTATIVE PREPARED BY ENGINEER FIRE PROFESSIONAL APPROVED BY DEPARTMENT OF FIRE SERVICE & CIVIL DEFENSE. Head Office: 38-46, Road: KaziAlauddin Road, Siddique Bazar, Dhaka. SCALE PAGE SIZE: 1:100 21-12-2021 A-3 DATE CONSULTANT: DESIGNER ARCHITECT PROPOSED 16 - STORIED RESIDENTIAL BUILDING AT PLOT NO-03, ROAD NO - 201, SECTOR NO-02, UNITED CITY, MADANI AVENUE, SATARKUL, DHAKA. CS DAG - 391, RS DAG - 233 & 234 MOUZA - SATARKUL, PS - BADDA, DHAKA. AHMED YOUSUF HOSSAIN S/O - Mohammad Abdul Bari MOTHERS NAME -Asiya Bari House # 7, Flat # C/2, Road-04. Gulshan # 1,Dhaka-1212. MART ENGINEERING & CONSULTANCY Address: House -10,Road-03,(1st FL), Middle Badda, Gulshan Badda Link ,Road, Dhaka-1212. Mobile : +88017 - 17432054 PAGE NO : 09
  • 11. LIVING 3.81mx4.95m LIFT 1.96mx1.52m FOYER 3.81mx1.96m GUEST BED 3.83mx4.37m TOILET 2.58mx1.52m PANTRY 1.68mx1.75m ROOM 2.10mx1.57m KITCHEN 2.63mx3.05m TOILET 1.14mx1.40m TOILET 2.58mx1.63m TOILET 2.59mx1.91m TOILET 2.21mx1.30m BED-2 3.83mx4.67m M.BED 4.17mx5.16m F.LIVING 3.81mx3.33m DINING 3.81mx4.93m BALCONY 2.13mx1.02m BALCONY 2.13mx2.03m BALCONY 2.44mx1.10m 13.55m 18.08m PLANTER BOX Front Balcony Excluded FAR and Ground Coverage Other balcony excluded FAR but included ground coverage UP DN FIRE STAIR 5.08mx2.00m STAIR 2.87mx4.27m Safety Lobby Safety Lobby ABC CO2 FHC Standpipe Riser & Drain Pipe Fire Hose Connection Ø65mm Landing valve 4 HOUR FIRE RATED WALL 4 HOUR FIRE RATED WALL LIFT LOBBY 1.68mx1.57m FIRE LIFT 1.96mx2.44m POSITIVE AIR PRESSURIZED. P ABC CO2 VER 1.27mx1.52m KITCHEN MECHANICAL VENTILATION SYSTEM SYMBOL SYMBOL NAME Q.T 00X13=00 Smoke Detector Fire Alarm Control Panel Horn With Light Manual call points P SYMBOL SYMBOL NAME Q.T SYMBOL SYMBOL NAME Q.T Standpipe Riser & Drain Pipe 01 Fire Hose Connection Class- III Fire Door 2 Rated 00 Sprinkler K- 11.2 PILLAR HYDRANT 00 FIRST AID BOX 13 Extinguisher (ABC & CO2) 00 00 2 way(65mm) Fire Department Connection 4 HOUR RATED WALL ABC CO2 Heat Detector FDC FACP POSITIVE AIR PRESSURIZED. 2ND FLOOR TO 14TH (TYPICAL) FLOOR: RESIDENTIAL AREA Floor Area: 223.27X13 =12,902.51 SQM Scale : 1:100 03X13=39 01X13=13 01X13=13 02X13=26 AS PER DRAWING N 01X13=13 FHC 01X13=13 03X13=39 17.45m PROJECT NAME & ADDRESS: OWNER'S NAME / REPRESENTATIVE PREPARED BY ENGINEER FIRE PROFESSIONAL APPROVED BY DEPARTMENT OF FIRE SERVICE & CIVIL DEFENSE. Head Office: 38-46, Road: KaziAlauddin Road, Siddique Bazar, Dhaka. SCALE PAGE SIZE: 1:100 21-12-2021 A-3 DATE CONSULTANT: DESIGNER ARCHITECT PROPOSED 16 - STORIED RESIDENTIAL BUILDING AT PLOT NO-03, ROAD NO - 201, SECTOR NO-02, UNITED CITY, MADANI AVENUE, SATARKUL, DHAKA. CS DAG - 391, RS DAG - 233 & 234 MOUZA - SATARKUL, PS - BADDA, DHAKA. AHMED YOUSUF HOSSAIN S/O - Mohammad Abdul Bari MOTHERS NAME -Asiya Bari House # 7, Flat # C/2, Road-04. Gulshan # 1,Dhaka-1212. MART ENGINEERING & CONSULTANCY Address: House -10,Road-03,(1st FL), Middle Badda, Gulshan Badda Link ,Road, Dhaka-1212. Mobile : +88017 - 17432054 PAGE NO : 10
  • 12. LIVING 3.81mx4.95m LIFT 1.96mx1.52m FOYER 3.81mx1.96m GUEST BED 3.83mx4.37m TOILET 2.58mx1.52m PANTRY 1.68mx1.75m ROOM 2.10mx1.57m KITCHEN 2.63mx3.05m TOILET 1.14mx1.40m TOILET 2.58mx1.63m TOILET 2.59mx1.91m TOILET 2.21mx1.30m BED-2 3.83mx4.67m M.BED 4.17mx5.16m F.LIVING 3.81mx3.33m DINING 3.81mx4.93m BALCONY 2.13mx1.02m BALCONY 2.13mx2.03m BALCONY 2.44mx1.10m 13.55m 18.08m PLANTER BOX Front Balcony Excluded FAR and Ground Coverage Other balcony excluded FAR but included ground coverage UP DN FIRE STAIR 5.08mx2.00m STAIR 2.87mx4.27m Safety Lobby Safety Lobby ABC CO2 FHC Standpipe Riser & Drain Pipe Fire Hose Connection Ø65mm Landing valve 4 HOUR FIRE RATED WALL 4 HOUR FIRE RATED WALL LIFT LOBBY 1.68mx1.57m FIRE LIFT 1.96mx2.44m POSITIVE AIR PRESSURIZED. P ABC CO2 VER 1.27mx1.52m KITCHEN MECHANICAL VENTILATION SYSTEM SYMBOL SYMBOL NAME Q.T 00 Smoke Detector Fire Alarm Control Panel Horn With Light Manual call points P SYMBOL SYMBOL NAME Q.T SYMBOL SYMBOL NAME Q.T Standpipe Riser & Drain Pipe 01 Fire Hose Connection Class- III Fire Door 2 Rated 00 Sprinkler K- 11.2 PILLAR HYDRANT 00 FIRST AID BOX 01 Extinguisher (ABC & CO2) 00 00 2 way(65mm) Fire Department Connection 4 HOUR RATED WALL ABC CO2 Heat Detector FDC FACP POSITIVE AIR PRESSURIZED. 8TH FLOOR: RESIDENTIAL & REFUGE AREA Floor Area: 223.27X13 =12,902.51 SQM Scale : 1:100 04 01 02 02 AS PER DRAWING N 01 FHC 01 04 17.45m REFUGE AREA PROJECT NAME & ADDRESS: OWNER'S NAME / REPRESENTATIVE PREPARED BY ENGINEER FIRE PROFESSIONAL APPROVED BY DEPARTMENT OF FIRE SERVICE & CIVIL DEFENSE. Head Office: 38-46, Road: KaziAlauddin Road, Siddique Bazar, Dhaka. SCALE PAGE SIZE: 1:100 21-12-2021 A-3 DATE CONSULTANT: DESIGNER ARCHITECT PROPOSED 16 - STORIED RESIDENTIAL BUILDING AT PLOT NO-03, ROAD NO - 201, SECTOR NO-02, UNITED CITY, MADANI AVENUE, SATARKUL, DHAKA. CS DAG - 391, RS DAG - 233 & 234 MOUZA - SATARKUL, PS - BADDA, DHAKA. AHMED YOUSUF HOSSAIN S/O - Mohammad Abdul Bari MOTHERS NAME -Asiya Bari House # 7, Flat # C/2, Road-04. Gulshan # 1,Dhaka-1212. MART ENGINEERING & CONSULTANCY Address: House -10,Road-03,(1st FL), Middle Badda, Gulshan Badda Link ,Road, Dhaka-1212. Mobile : +88017 - 17432054 PAGE NO : 11
  • 13. LIFT MACHINE ROOM 1.96mx6.05m 4.16m 1.09m 13.55m 1.85m 7.04m 2.90m 7.52m 13.55m 8.23m 2.67m 3.81m 4.50m COMMON ROOM 7.76mx7.21m 9.86m Raised 1.75m Raised 1.75m DN 1.78m DN TOILET 2.73mx1.27m FIRE STAIR 5.08mx2.00m STAIR 2.87mx4.27m Safety Lobby Safety Lobby ABC CO2 FHC Standpipe Riser & Drain Pipe Fire Hose Connection Ø65mm Landing valve 4 HOUR RATED WALL 4 HOUR FIRE RATED WALL P POSITIVE AIR PRESSURIZED. R O O F W A T E R D R A I N A G E SLOPE 1:200 R O O F W A T E R D R A I N A G E S L O P E 1 : 2 0 0 R O O F W A T E R D R A I N A G E S L O P E 1 : 2 0 0 R O O F W A T E R D R A I N A G E S L O P E 1 : 2 0 0 OPEN SKY SYMBOL SYMBOL NAME Q.T 00 Smoke Detector Fire Alarm Control Panel Horn With Light Manual call points P SYMBOL SYMBOL NAME Q.T SYMBOL SYMBOL NAME Q.T Standpipe Riser & Drain Pipe 01 Fire Hose Connection Class- III Fire Door 2 Rated 01 Class-I Hose Connection PILLAR HYDRANT 00 FIRST AID BOX 01 Extinguisher (ABC & CO2) 00 00 2 way(65mm) Fire Department Connection 4 HOUR RATED WALL ABC CO2 Heat Detector FDC FACP POSITIVE AIR PRESSURIZED. 15TH FLOOR & ROOF FLOOR: RESIDENTIAL AREA Floor Area:105.90 SQM Scale : 1:100 08 02 03 02 01 03 AS PER DRAWING 02 ABC CO2 ABC CO2 P FHC N PROJECT NAME & ADDRESS: OWNER'S NAME / REPRESENTATIVE PREPARED BY ENGINEER FIRE PROFESSIONAL APPROVED BY DEPARTMENT OF FIRE SERVICE & CIVIL DEFENSE. Head Office: 38-46, Road: KaziAlauddin Road, Siddique Bazar, Dhaka. SCALE PAGE SIZE: 1:100 21-12-2021 A-3 DATE CONSULTANT: DESIGNER ARCHITECT PROPOSED 16 - STORIED RESIDENTIAL BUILDING AT PLOT NO-03, ROAD NO - 201, SECTOR NO-02, UNITED CITY, MADANI AVENUE, SATARKUL, DHAKA. CS DAG - 391, RS DAG - 233 & 234 MOUZA - SATARKUL, PS - BADDA, DHAKA. AHMED YOUSUF HOSSAIN S/O - Mohammad Abdul Bari MOTHERS NAME -Asiya Bari House # 7, Flat # C/2, Road-04. Gulshan # 1,Dhaka-1212. MART ENGINEERING & CONSULTANCY Address: House -10,Road-03,(1st FL), Middle Badda, Gulshan Badda Link ,Road, Dhaka-1212. Mobile : +88017 - 17432054 PAGE NO : 12
  • 14. ROOF OF STAIR & O. H. W. R. 20000 LITTER ROOF OF COMMON ROOM ROOF OF LIFT MACHINE ROOM ROOF OF FIRE STAIR OPEN SKY 10' 8' Grounding Electrode No:01 Grounding Electrode (Size: Dia12.7mm) Bounding Conductor (Width 12.7mm & Thickness 1.30mm) Down Conductor-01 Size: 12mm Dia Copper Rod 10' 8' Grounding Electrode No:02 Grounding Electrode (Size: Dia12.7mm) Bounding Conductor (Width 12.7mm & Thickness 1.30mm) Down Conductor-01 Size: 12mm Dia Copper Rod 10' 8' Grounding Electrode No:04 Grounding Electrode (Size: Dia12.7mm) Bounding Conductor (Width 12.7mm & Thickness 1.30mm) Down Conductor-01 Size: 12mm Dia Copper Rod 10' 8' Grounding Electrode No:03 Grounding Electrode (Size: Dia12.7mm) Bounding Conductor (Width 12.7mm & Thickness 1.30mm) Down Conductor-01 Size: 12mm Dia Copper Rod Roof Floor : Proposed Lighting Protection System (LPS). LEGEND Down Conductor (Solid Rod ɸ-12mm Copper) Bounding Conductor (Solid or Standard ɸ-17AWG Copper) Earth Symbol Earthing Rod (ɸ-12mm Copper) Air Terminal (ɸ-12mm Copper) In The Periphery top of the Building, Hight 2ft. Calculation of Down Conductor, DC = Total Periphery/100 = 569'/100 = 5.69 = 06 Pcs Required Materials Calss-II Follow Standard- NFPA780 Air Terminal Top (ɸ-12mm Copper) In The Periphery top of the Building, Hight 2ft. PROJECT NAME & ADDRESS: OWNER'S NAME / REPRESENTATIVE PREPARED BY ENGINEER FIRE PROFESSIONAL APPROVED BY DEPARTMENT OF FIRE SERVICE & CIVIL DEFENSE. Head Office: 38-46, Road: KaziAlauddin Road, Siddique Bazar, Dhaka. SCALE PAGE SIZE: 1:100 21-12-2021 A-3 DATE CONSULTANT: DESIGNER ARCHITECT PROPOSED 16 - STORIED RESIDENTIAL BUILDING AT PLOT NO-03, ROAD NO - 201, SECTOR NO-02, UNITED CITY, MADANI AVENUE, SATARKUL, DHAKA. CS DAG - 391, RS DAG - 233 & 234 MOUZA - SATARKUL, PS - BADDA, DHAKA. AHMED YOUSUF HOSSAIN S/O - Mohammad Abdul Bari MOTHERS NAME -Asiya Bari House # 7, Flat # C/2, Road-04. Gulshan # 1,Dhaka-1212. MART ENGINEERING & CONSULTANCY Address: House -10,Road-03,(1st FL), Middle Badda, Gulshan Badda Link ,Road, Dhaka-1212. Mobile : +88017 - 17432054 PAGE NO : 13
  • 15. 1.75m 1.25m 3.00m NORTH ELEVATION SCALE : 1 : 100 LIGHTNING ARRESTOR. SECURITY LIGHT ROAD LEVEL ± 00 2ND FLOOR LEVEL+ 7.32m 3RD FLOOR LEVEL+ 10.36m 5TH FLOOR LEVEL + 16.46m 4TH FLOOR LEVEL + 13.41m PARAPET TOP + 48.46m 1ST FLOOR LEVEL +4.27m O.H.W.T. TOP + 51.94m PLINTH LEVEL + 0.91m 6TH FLOOR LEVEL + 19.51m 7TH FLOOR LEVEL + 22.56m 8TH FLOOR LEVEL + 25.60m 9TH FLOOR LEVEL + 28.65m 10TH FLOOR LEVEL + 31.70m 11TH FLOOR LEVEL + 34.75m 12TH FLOOR LEVEL + 37.80m 13TH FLOOR LEVEL + 40.84m 14TH FLOOR LEVEL + 43.89m 15TH FLOOR LEVEL + 46.94m O.H.W.T LEVEL + 0.76m 1.75m 1.25m 3.00m LEVEL + 0.91m 0.91m 0.91m 0.91m 0.91m 0.91m 0.91m 0.91m 0.91m 0.91m 0.91m 0.91m 0.91m 0.91m 0.91m 0.91m 0.91m 0.91m 0.91m 0.91m 0.91m 0.91m 0.91m 0.91m 0.91m 0.91m 0.91m 0.91m 0.91m 0.91m 0.91m 3.05m 3.51m 3.05m 3.05m 3.05m 3.05m 3.05m 3.05m 3.05m 3.05m 3.05m 3.05m 3.05m 3.05m 3.05m 3.05m 3.05m 1.96m 51.94m SECTION A-A SCALE : 1 : 100 ROAD LEVEL ± 00 2ND FLOOR LEVEL+ 7.32m 3RD FLOOR LEVEL+ 10.36m 5TH FLOOR LEVEL + 16.46m 4TH FLOOR LEVEL + 13.41m PARAPET TOP + 48.46m 1ST FLOOR LEVEL +4.27m O.H.W.T. TOP + 51.94m PLINTH LEVEL + 0.91m 6TH FLOOR LEVEL + 19.51m 7TH FLOOR LEVEL + 22.56m 8TH FLOOR LEVEL + 25.60m 9TH FLOOR LEVEL + 28.65m 10TH FLOOR LEVEL + 31.70m 11TH FLOOR LEVEL + 34.75m 12TH FLOOR LEVEL + 37.80m 13TH FLOOR LEVEL + 40.84m 14TH FLOOR LEVEL + 43.89m 15TH FLOOR LEVEL + 46.94m LIGHTNING ARRESTOR. SECURITY LIGHT ELEVATION & SECTION VIEW PROJECT NAME & ADDRESS: OWNER'S NAME / REPRESENTATIVE PREPARED BY ENGINEER FIRE PROFESSIONAL APPROVED BY DEPARTMENT OF FIRE SERVICE & CIVIL DEFENSE. Head Office: 38-46, Road: KaziAlauddin Road, Siddique Bazar, Dhaka. SCALE PAGE SIZE: 1:100 21-12-2021 A-3 DATE CONSULTANT: DESIGNER ARCHITECT PROPOSED 16 - STORIED RESIDENTIAL BUILDING AT PLOT NO-03, ROAD NO - 201, SECTOR NO-02, UNITED CITY, MADANI AVENUE, SATARKUL, DHAKA. CS DAG - 391, RS DAG - 233 & 234 MOUZA - SATARKUL, PS - BADDA, DHAKA. AHMED YOUSUF HOSSAIN S/O - Mohammad Abdul Bari MOTHERS NAME -Asiya Bari House # 7, Flat # C/2, Road-04. Gulshan # 1,Dhaka-1212. MART ENGINEERING & CONSULTANCY Address: House -10,Road-03,(1st FL), Middle Badda, Gulshan Badda Link ,Road, Dhaka-1212. Mobile : +88017 - 17432054 PAGE NO : 14
  • 16. +10'-0" 1'-8" Delivery Pipe , Ø 125 mm Delivery Pipe , Ø 50 mm Delivery Pipe , Ø 125 mm Ø150 mm Header Pipe Level (-) 3'-0" Ø125 mm Suction for Engine Driven Fire Pump, Level (-) 12'-0" Ø65 mm Suction for Motor Driven Jockey Pump, Level (-) 12'-0" Ø125 mm Suction for Motor Driven Fire Pump, Level (-) 12'-0" P SITIVE SUCTI N FIRE PUMP SCHEM TIC DI GR M ND INST LL TI N DET ILING Ø125mm Relief valve discharge Pipe, Level (+) 0'-6" Ø150mm Delivery Pipe, Level (-) 3'-0" 64'-1" Ø150mm Pipe from Deep Tubewell to Fill the Underground Water Reservore, Level (-) 1'-0" Level (-) 0'-0" Level (+) 0'-0" Water Level (-) 1'-0" 32'-4" TS TS TS Water Level Gauge Ø150mm Pipe WF TS 10'-0" Ø125mm Test Header Pipe, Level (+) 0'-6" Ø150mm Flow Meter Pipe, Level (+) 0'-6" WF Ø50mm Drain Pipe To Nearest Drain Pit AIM AIM Ø150mm Standpipe Riser-01 Class-III Hose Connection Ø65mm Branch Pipe Proposed Fire Pump Schedule (Brand: , ......) Type of Pump Type of Driver Rated Capacity (US GPM) Rated Pressure (bar.g) Rated Head (FT.) M a i n F i r e P u m p ( E P ) Stand By Fire Pump (DP) Jockey Pump (JP) 500.00 Horizontal Spilt Case Centifugal Vertical Multi-stage Centifugal Electrical Motor Diesel Engine Electrical Motor 100.00 10.00 Horizontal Spilt Case Centifugal Pump RPM 2900 500.00 100.00 10.00 2900 25.00 110.00 11.0 3000 Class- I Landing valve (Ø65mm Landing Valve) Standpipe Riser & Drain Pipe Pillar Hydrant (2xØ65mm/Ø150mm) Four Way Fire Department Connection (4xØ65mm/Ø150mm) LEGEND S MB L S MB L N ME T 00 14 01 01 01 Class - III Hose Connection (Ø40mm Pressure Hydrant Valve with Ø38mm Canvas Hose & Ø38mm Variable Nozzle & Within Cabinate) FIRE DEPARTMENT CONNECTION - 2 WAY(65MM) NON RETURN VALVE: 100MM Pillar Hydrant AIR RELIFE VALVE PRESSURE GAUGE BALL VALVE BALL VALVE Ø150mm Standpipe Riser-01 FDC L +10'-0" Ø65mm Branch Pipe N TO L Class-III Hose Connection Ø65mm Branch Pipe ROO L FDC Ø40mm Branch Pipe Ø40mm Branch Pipe PROPOSED UNDER GROUND WATER RESERVOIR 60,000 US GALLON Class-III Hose Connection Ø65mm Branch Pipe Ø40mm Branch Pipe ROUN L +10'-0" Ø65mm Branch Pipe Class-III Hose Connection Ø65mm Branch Pipe Ø40mm Branch Pipe Ø50mm Pipe W F AIM AIM To Nearest Drain Pit Zone Control Valve Sprinkler Ø150mm Cross main HOSE NOZZE SPRING LOCK HANDLE 1½" Ø CANVASS HOSE 2½" Ø LANDING VALVE FIRE HOSE CABINET (2'-4"X10"X2'-8") WIRRED GLASS 1½" Ø CONTROLLED PRESSURE HYDRNT VALVE 6" Ø STANDPIPE RISER BALL VALVE 2½" Ø M.S. PIPE PROJECT NAME & ADDRESS: OWNER'S NAME / REPRESENTATIVE PREPARED BY ENGINEER FIRE PROFESSIONAL APPROVED BY DEPARTMENT OF FIRE SERVICE & CIVIL DEFENSE. Head Office: 38-46, Road: KaziAlauddin Road, Siddique Bazar, Dhaka. SCALE PAGE SIZE: 1:100 21-12-2021 A-3 DATE CONSULTANT: DESIGNER ARCHITECT PROPOSED 16 - STORIED RESIDENTIAL BUILDING AT PLOT NO-03, ROAD NO - 201, SECTOR NO-02, UNITED CITY, MADANI AVENUE, SATARKUL, DHAKA. CS DAG - 391, RS DAG - 233 & 234 MOUZA - SATARKUL, PS - BADDA, DHAKA. AHMED YOUSUF HOSSAIN S/O - Mohammad Abdul Bari MOTHERS NAME -Asiya Bari House # 7, Flat # C/2, Road-04. Gulshan # 1,Dhaka-1212. MART ENGINEERING & CONSULTANCY Address: House -10,Road-03,(1st FL), Middle Badda, Gulshan Badda Link ,Road, Dhaka-1212. Mobile : +88017 - 17432054 PAGE NO : 15
  • 17. SYMBOL LEGEND WITH SPECIFICATION SYMBOL NAME Horn With Light Smoke Detector Heat Detector Malti Detector Addressable Manual call points Addressable Fire Alarm Control Panel Addressable Output Module P Addressable Input Module AOM AIM SYMBOL SYMBOL NAME 03 06 00 22 Q.T 19 00 12 Q.T AIM AIM AIM AIM AIM AIM AIM AIM AIM AIM MAIN FIRE ALARM CONTROL PANEL, No-01 2 LOOPS BATTERY CAPACITY = 10 AH SECURITY ROOM (GF) AUX-ILIARY POWER SUPPLY (NAC CIRCUIT) SOFTWARE INTERFACE WITH BMS SYSTEM INTERFACE WITH PUBLIC ADDRESS 3 x 2.5rm wire from primary power source LOOP 2 LOOP 1 EOLR FIRE ALARM RISER DIAGRAM P P P P P P P P P P P P P P P P P EOLR FACP PROJECT NAME & ADDRESS: OWNER'S NAME / REPRESENTATIVE PREPARED BY ENGINEER FIRE PROFESSIONAL APPROVED BY DEPARTMENT OF FIRE SERVICE & CIVIL DEFENSE. Head Office: 38-46, Road: KaziAlauddin Road, Siddique Bazar, Dhaka. SCALE PAGE SIZE: 1:100 21-12-2021 A-3 DATE CONSULTANT: DESIGNER ARCHITECT PROPOSED 16 - STORIED RESIDENTIAL BUILDING AT PLOT NO-03, ROAD NO - 201, SECTOR NO-02, UNITED CITY, MADANI AVENUE, SATARKUL, DHAKA. CS DAG - 391, RS DAG - 233 & 234 MOUZA - SATARKUL, PS - BADDA, DHAKA. AHMED YOUSUF HOSSAIN S/O - Mohammad Abdul Bari MOTHERS NAME -Asiya Bari House # 7, Flat # C/2, Road-04. Gulshan # 1,Dhaka-1212. MART ENGINEERING & CONSULTANCY Address: House -10,Road-03,(1st FL), Middle Badda, Gulshan Badda Link ,Road, Dhaka-1212. Mobile : +88017 - 17432054 PAGE NO : 16
  • 18. REB SUPPLY M METER 11KV DROP OUT FUSE(100A) 11 KV LIGHTNING ARRESTER G 12.7mm Dia Cu Conductor (Body Earthing) Earth Pit-9 Earth Pit-8 Earth Pit-7 12.7mm Dia Cu Conductor 12.7mm Dia Cu Conductor 100KVA Diesel Generator 440V, 50Hz, Prime-220KVA, Standby-200KVA 12.7mm Dia Cu Conductor 12.7mm Dia Cu Conductor 12.7mm Dia Cu Conductor 12.7mm Dia Cu Conductor EARTH PIT-6 EARTH PIT-5 EARTH PIT-4 EARTH PIT-3 (Neutral Earthing) (Neutral Earthing) (Body Earthing) (Body Earthing) 100A ATS Panel (Body Earthing) 150KVA TRANSFORMER 11KV / 415V, Dyn11, 50Hz, Step Down. %Z=6, OIL TYPE 1CX4X400RM NYY CABLE(TP+N) 630A TP MCCB Adj-1 LT Panel Load=497kw Diversity Factor-40% (Load=199KW) 3X50RM (NYSEYFGbY) HT CABLE 1CX4X150RM NYY CABLE(TP+N) 1CX4X150RM NYY CABLE(TP+N) (Neutral Earthing) PROPOSED SINGLE LINE DIAGRAM (SLD) 90KVAR Door ECC=1X4.0 rm CKT- 00 1CX4XX50 Sqmm (TP+N) NYY ECC- 1CX1X25 Sqmm BYA CKT- 1 CKT- 2 CKT- 3 CKT- 4 CKT- 5 CKT- 6 CKT- 7 CKT- 8 CKT- 9 CKT- 10 CKT- 11 CKT- 12 CKT- 13 CKT- 14 Earth Pit-10 12.7mm Dia Cu Conductor (Body Earthing) Bus Bar- 372A (TP+N) & ECC- 186A, 30mmX8mm (TP+N) CU BUS BAR +20mmX6mm ECC 150A TP MCCB CKT- 15 CKT- 16 CKT- 17 CKT- 18 CKT- 19 CKT- 20 CKT- 21 CKT- 22 CKT- 23 CKT- 24 CKT- 25 40A DP MCB 1CX2X10 Sqmm (SP+N) BYA ECC 1CX1X6 Sqmm BYA 40A DP MCB 1CX2X10 Sqmm (SP+N) BYA ECC 1CX1X6 Sqmm BYA 40A DP MCB 1CX2X10 Sqmm (SP+N) BYA ECC 1CX1X6 Sqmm BYA 40A DP MCB 1CX2X10 Sqmm (SP+N) BYA ECC 1CX1X6 Sqmm BYA 40A DP MCB 1CX2X10 Sqmm (SP+N) BYA ECC 1CX1X6 Sqmm BYA 40A DP MCB 1CX2X10 Sqmm (SP+N) BYA ECC 1CX1X6 Sqmm BYA 40A DP MCB 1CX2X10 Sqmm (SP+N) BYA ECC 1CX1X6 Sqmm BYA 40A DP MCB 1CX2X10 Sqmm (SP+N) BYA ECC 1CX1X6 Sqmm BYA 40A DP MCB 1CX2X10 Sqmm (SP+N) BYA ECC 1CX1X6 Sqmm BYA 40A DP MCB 1CX2X10 Sqmm (SP+N) BYA ECC 1CX1X6 Sqmm BYA 40A DP MCB 1CX2X10 Sqmm (SP+N) BYA ECC 1CX1X6 Sqmm BYA 40A DP MCB 1CX2X10 Sqmm (SP+N) BYA ECC 1CX1X6 Sqmm BYA 40A DP MCB 1CX2X10 Sqmm (SP+N) BYA ECC 1CX1X6 Sqmm BYA 40A DP MCB 1CX2X10 Sqmm (SP+N) BYA ECC 1CX1X6 Sqmm BYA 40A DP MCB 1CX2X10 Sqmm (SP+N) BYA ECC 1CX1X6 Sqmm BYA 40A DP MCB 1CX2X10 Sqmm (SP+N) BYA ECC 1CX1X6 Sqmm BYA 40A DP MCB 1CX2X10 Sqmm (SP+N) BYA ECC 1CX1X6 Sqmm BYA 40A DP MCB 1CX2X10 Sqmm (SP+N) BYA ECC 1CX1X6 Sqmm BYA 40A DP MCB 1CX2X10 Sqmm (SP+N) BYA ECC 1CX1X6 Sqmm BYA 40A DP MCB 1CX2X10 Sqmm (SP+N) BYA ECC 1CX1X6 Sqmm BYA 40A DP MCB 1CX2X10 Sqmm (SP+N) BYA ECC 1CX1X6 Sqmm BYA 40A DP MCB 1CX2X10 Sqmm (SP+N) BYA ECC 1CX1X6 Sqmm BYA 40A DP MCB 1CX2X10 Sqmm (SP+N) BYA ECC 1CX1X6 Sqmm BYA 40A DP MCB 1CX2X10 Sqmm (SP+N) BYA ECC 1CX1X6 Sqmm BYA 40A DP MCB 1CX2X10 Sqmm (SP+N) BYA ECC 1CX1X6 Sqmm BYA 40A DP MCB 1CX2X10 Sqmm (SP+N) BYA ECC 1CX1X6 Sqmm BYA CKT- 26 CKT- 27 CKT- 28 CKT- 29 CKT- 30 40A DP MCB 1CX2X10 Sqmm (SP+N) BYA ECC 1CX1X6 Sqmm BYA CKT- 31 40A DP MCB 1CX2X10 Sqmm (SP+N) BYA ECC 1CX1X6 Sqmm BYA CKT- 32 40A DP MCB 1CX2X10 Sqmm (SP+N) BYA ECC 1CX1X6 Sqmm BYA CKT- 33 DB-1 1ST F UNIT-A Load=7KW Diversity Factor-40% (Load=2.8KW) DB-2 2ND F UNIT-A Load=7KW Diversity Factor-40% (Load=2.8KW) DB-3 3RD F UNIT-A Load=7KW Diversity Factor-40% (Load=2.8KW) DB-4 4TH F UNIT-A Load=7KW Diversity Factor-40% (Load=2.8KW) DB-5 5TH F UNIT-A Load=7KW Diversity Factor-40% (Load=2.8KW) DB-6 6TH F UNIT-A Load=7KW Diversity Factor-40% (Load=2.8KW) DB-7 7TH F UNIT-A Load=7KW Diversity Factor-40% (Load=2.8KW) DB-8 8TH F UNIT-A Load=7KW Diversity Factor-40% (Load=2.8KW) DB-1 1ST F UNIT-B Load=7KW Diversity Factor-40% (Load=2.8KW) DB-1 1ST F UNIT-C Load=7KW Diversity Factor-40% (Load=2.8KW) DB-1 1ST F UNIT-D Load=7KW Diversity Factor-40% (Load=2.8KW) DB-2 2ND F UNIT-B Load=7KW Diversity Factor-40% (Load=2.8KW) DB-2 2ND F UNIT-C Load=7KW Diversity Factor-40% (Load=2.8KW) DB-2 2ND F UNIT-D Load=7KW Diversity Factor-40% (Load=2.8KW) DB-3 3RD F UNIT-B Load=7KW Diversity Factor-40% (Load=2.8KW) DB-3 3RD F UNIT-C Load=7KW Diversity Factor-40% (Load=2.8KW) DB-3 3RD F UNIT-D Load=7KW Diversity Factor-40% (Load=2.8KW) DB-4 4TH F UNIT-B Load=7KW Diversity Factor-40% (Load=2.8KW) DB-4 4TH F UNIT-C Load=7KW Diversity Factor-40% (Load=2.8KW) DB-4 4TH F UNIT-D Load=7KW Diversity Factor-40% (Load=2.8KW) DB-5 5TH F UNIT-B Load=7KW Diversity Factor-40% (Load=2.8KW) DB-5 5TH F UNIT-C Load=7KW Diversity Factor-40% (Load=2.8KW) DB-5 5TH F UNIT-D Load=7KW Diversity Factor-40% (Load=2.8KW) DB-6 6TH F UNIT-B Load=7KW Diversity Factor-40% (Load=2.8KW) DB-6 6TH F UNIT-C Load=7KW Diversity Factor-40% (Load=2.8KW) DB-6 6TH F UNIT-D Load=7KW Diversity Factor-40% (Load=2.8KW) DB-7 7TH F UNIT-B Load=7KW Diversity Factor-40% (Load=2.8KW) DB-7 7TH F UNIT-C Load=7KW Diversity Factor-40% (Load=2.8KW) DB-7 7TH F UNIT-D Load=7KW Diversity Factor-40% (Load=2.8KW) CKT- 34 CKT- 35 CKT- 36 CKT- 37 CKT- 38 CKT- 39 CKT- 40 CKT- 41 CKT- 42 CKT- 43 CKT- 44 CKT- 45 CKT- 46 CKT- 47 CKT- 48 40A DP MCB 1CX2X10 Sqmm (SP+N) BYA ECC 1CX1X6 Sqmm BYA 40A DP MCB 1CX2X10 Sqmm (SP+N) BYA ECC 1CX1X6 Sqmm BYA 40A DP MCB 1CX2X10 Sqmm (SP+N) BYA ECC 1CX1X6 Sqmm BYA 40A DP MCB 1CX2X10 Sqmm (SP+N) BYA ECC 1CX1X6 Sqmm BYA 40A DP MCB 1CX2X10 Sqmm (SP+N) BYA ECC 1CX1X6 Sqmm BYA 40A DP MCB 1CX2X10 Sqmm (SP+N) BYA ECC 1CX1X6 Sqmm BYA 40A DP MCB 1CX2X10 Sqmm (SP+N) BYA ECC 1CX1X6 Sqmm BYA 40A DP MCB 1CX2X10 Sqmm (SP+N) BYA ECC 1CX1X6 Sqmm BYA 40A DP MCB 1CX2X10 Sqmm (SP+N) BYA ECC 1CX1X6 Sqmm BYA 40A DP MCB 1CX2X10 Sqmm (SP+N) BYA ECC 1CX1X6 Sqmm BYA 40A DP MCB 1CX2X10 Sqmm (SP+N) BYA ECC 1CX1X6 Sqmm BYA 40A DP MCB 1CX2X10 Sqmm (SP+N) BYA ECC 1CX1X6 Sqmm BYA 40A DP MCB 1CX2X10 Sqmm (SP+N) BYA ECC 1CX1X6 Sqmm BYA 40A DP MCB 1CX2X10 Sqmm (SP+N) BYA ECC 1CX1X6 Sqmm BYA 40A DP MCB 1CX2X10 Sqmm (SP+N) BYA ECC 1CX1X6 Sqmm BYA 40A DP MCB 1CX2X10 Sqmm (SP+N) BYA ECC 1CX1X6 Sqmm BYA 40A DP MCB 1CX2X10 Sqmm (SP+N) BYA ECC 1CX1X6 Sqmm BYA 40A DP MCB 1CX2X10 Sqmm (SP+N) BYA ECC 1CX1X6 Sqmm BYA 40A DP MCB 1CX2X10 Sqmm (SP+N) BYA ECC 1CX1X6 Sqmm BYA 40A DP MCB 1CX2X10 Sqmm (SP+N) BYA ECC 1CX1X6 Sqmm BYA CKT- 49 CKT- 51 CKT- 52 CKT- 53 40A DP MCB 1CX2X10 Sqmm (SP+N) BYA ECC 1CX1X6 Sqmm BYA CKT- 54 40A DP MCB 1CX2X10 Sqmm (SP+N) BYA ECC 1CX1X6 Sqmm BYA CKT- 55 DB-8 8TH F UNIT-B Load=7KW Diversity Factor-40% (Load=2.8KW) DB-8 8TH F UNIT-C Load=7KW Diversity Factor-40% (Load=2.8KW) DB-8 8TH F UNIT-D Load=7KW Diversity Factor-40% (Load=2.8KW) CKT- 50 DB-9 9TH F UNIT-A Load=7KW Diversity Factor-40% (Load=2.8KW) DB-9 9TH F UNIT-B Load=7KW Diversity Factor-40% (Load=2.8KW) DB-9 9TH F UNIT-C Load=7KW Diversity Factor-40% (Load=2.8KW) DB-9 9TH F UNIT-D Load=7KW Diversity Factor-40% (Load=2.8KW) DB-10 10TH F UNIT-A Load=7KW Diversity Factor-40% (Load=2.8KW) DB-10 10TH F UNIT-B Load=7KW Diversity Factor-40% (Load=2.8KW) DB-10 10TH F UNIT-C Load=7KW Diversity Factor-40% (Load=2.8KW) DB-10 10TH F UNIT-D Load=7KW Diversity Factor-40% (Load=2.8KW) DB-11 11TH F UNIT-A Load=7KW Diversity Factor-40% (Load=2.8KW) DB-11 11TH F UNIT-B Load=7KW Diversity Factor-40% (Load=2.8KW) DB-11 11TH F UNIT-C Load=7KW Diversity Factor-40% (Load=2.8KW) DB-11 11TH F UNIT-D Load=7KW Diversity Factor-40% (Load=2.8KW) DB-12 12TH F UNIT-A Load=7KW Diversity Factor-40% (Load=2.8KW) DB-12 12TH F UNIT-B Load=7KW Diversity Factor-40% (Load=2.8KW) DB-12 12TH F UNIT-C Load=7KW Diversity Factor-40% (Load=2.8KW) DB-12 12TH F UNIT-D Load=7KW Diversity Factor-40% (Load=2.8KW) DB-13 13TH F UNIT-A Load=7KW Diversity Factor-40% (Load=2.8KW) 40A DP MCB 1CX2X10 Sqmm (SP+N) BYA ECC 1CX1X6 Sqmm BYA CKT- 56 40A DP MCB CKT- 57 40A DP MCB CKT- 58 DB-13 13TH F UNIT-B Load=7KW Diversity Factor-40% (Load=2.8KW) DB-13 13TH F UNIT-C Load=7KW Diversity Factor-40% (Load=2.8KW) DB-13 13TH F UNIT-D Load=7KW Diversity Factor-40% (Load=2.8KW) SPARE SPARE R B Y B R B Y R B Y R B Y R B Y R B Y R B Y R B Y R B Y R B Y R B Y R B Y R B Y R B Y R B Y R B Y R B Y R B Y R Y 1CX4XX70 Sqmm (TP+N) NYY ECC- 1CX1X35 Sqmm BYA 200A TP MCCB R B YFire Pump DB Load=80kw 1CX4XX70 Sqmm (TP+N) NYY ECC- 1CX1X35 Sqmm BYA 40A TP MCCB Lift DB Load=15kw 1CX4XX70 Sqmm (TP+N) NYY ECC- 1CX1X35 Sqmm BYA 40A TP MCCB Lift DB Load=15kw 1CX4XX70 Sqmm (TP+N) NYY ECC- 1CX1X35 Sqmm BYA 40A TP MCCB Lift DB Load=15kw R B Y R B Y R B Y CKT-59 1CX4XX70 Sqmm (TP+N) NYY ECC- 1CX1X35 Sqmm BYA 40A TP MCCB Lift DB Load=15kw R B Y LBS 12.7mm Dia Cu Conductor EARTH PIT-2 12.7mm Dia Cu Conductor EARTH PIT-1 PROJECT NAME & ADDRESS: OWNER'S NAME / REPRESENTATIVE PREPARED BY ENGINEER FIRE PROFESSIONAL APPROVED BY DEPARTMENT OF FIRE SERVICE & CIVIL DEFENSE. Head Office: 38-46, Road: KaziAlauddin Road, Siddique Bazar, Dhaka. SCALE PAGE SIZE: 1:100 21-12-2021 A-3 DATE CONSULTANT: DESIGNER ARCHITECT PROPOSED 16 - STORIED RESIDENTIAL BUILDING AT PLOT NO-03, ROAD NO - 201, SECTOR NO-02, UNITED CITY, MADANI AVENUE, SATARKUL, DHAKA. CS DAG - 391, RS DAG - 233 & 234 MOUZA - SATARKUL, PS - BADDA, DHAKA. AHMED YOUSUF HOSSAIN S/O - Mohammad Abdul Bari MOTHERS NAME -Asiya Bari House # 7, Flat # C/2, Road-04. Gulshan # 1,Dhaka-1212. MART ENGINEERING & CONSULTANCY Address: House -10,Road-03,(1st FL), Middle Badda, Gulshan Badda Link ,Road, Dhaka-1212. Mobile : +88017 - 17432054 PAGE NO : 17